Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

TEMECULA HEALTHCARE CENTER

TEMECULA, CA · 115 certified beds · Last Life Safety survey April 17, 2025

CMS Certification Number 555923 · first certified July 2021

Ownership

Operated by GENERATIONS HEALTHCARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

12
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
1
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within CA

12 citations — more than 17% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 4.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: April 2026 to October 2026. This facility’s last Life Safety survey was April 2025. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about TEMECULA HEALTHCARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 12 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.

This facility12CA median19National median11
Citations on file over three years, compared
MeasureCitations
This facility12
Median facility in CA19
Median facility nationally11

Survey history

Citations at each Life Safety survey
22021-0672024-0232025-04
Citations at each Life Safety survey
Survey dateCitations
June 23, 20212
February 25, 20247
April 17, 20253

Most-cited tags

Most-cited tags at this facility
K-03552K-07121K-09181K-07111K-03631K-02221K-03451K-03721
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-04-17
K-0712Have simulated fire drills held at unexpected times.12024-02-25
K-0918Have generator or other power source capable of supplying service within 10 seconds.12024-02-25
K-0711Provide a written emergency evacuation plan.12025-04-17
K-0363Install corridor and hallway doors that block smoke.12024-02-25
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12025-04-17
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12024-02-25
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12024-02-25

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 7
  • Miscellaneous Deficiencies 2
  • Egress Deficiencies 1
  • Gas, Vacuum, and Electrical Systems Deficiencies 1
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies7
Miscellaneous Deficiencies2
Egress Deficiencies1
Gas, Vacuum, and Electrical Systems Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 17, 2025 — 3 citations

Citations issued on April 17, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 5, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 5, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (May 5, 2025)

February 25, 2024 — 7 citations

Citations issued on February 25, 2024
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 12, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 12, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 12, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 12, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 12, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 12, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 12, 2024)

June 23, 2021 — 2 citations

Citations issued on June 23, 2021
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 13, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 13, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.