Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
VISALIA POST ACUTE
VISALIA, CA · 176 certified beds · Last Life Safety survey March 6, 2026
CMS Certification Number 055604 · first certified August 1985
Ownership
Operated by PACS GROUP · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within CA
38 citations — more than 95% of the 1,165 certified nursing homes in CA. Compared within CA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 10 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens March 2027 — about 5 months from now. This facility’s last Life Safety survey was March 2026. Facilities in CA are typically surveyed 12–18 months after the last one (median 14), measured over 1,766 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about VISALIA POST ACUTE
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
11 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
How that compares
Compared with the median facility in CA, and nationally. Surveyors differ markedly between states, so the CA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 38 |
| Median facility in CA | 19 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| December 7, 2023 | 12 |
| February 3, 2025 | 16 |
| March 6, 2026 | 10 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-03-06 |
| E-0039 | Conduct testing and exercise requirements. | 3 | 2026-03-06 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-03-06 |
| E-0041 | Implement emergency and standby power systems. | 3 | 2026-03-06 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 2 | 2025-02-03 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2025-02-03 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2026-03-06 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 2 | 2025-02-03 |
What the citations cover
- Emergency Preparedness Deficiencies 11
- Smoke Deficiencies 10
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Egress Deficiencies 5
- Other 6
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 11 |
| Smoke Deficiencies | 10 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Egress Deficiencies | 5 |
| Services Deficiencies | 3 |
| Miscellaneous Deficiencies | 2 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 6, 2026 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (March 30, 2026) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (March 30, 2026) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (March 18, 2026) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (March 30, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (March 30, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 30, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 30, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 18, 2026) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 18, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 30, 2026) |
February 3, 2025 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (February 13, 2025) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (February 13, 2025) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (February 13, 2025) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (February 13, 2025) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (February 13, 2025) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (February 18, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 13, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 13, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (February 18, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (February 13, 2025) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (February 21, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (February 13, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (March 5, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (February 13, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 13, 2025) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (March 13, 2025) |
December 7, 2023 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (January 9, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (January 9, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 9, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (January 9, 2024) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.