Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BERKLEY MANOR CARE CENTER

DENVER, CO · 118 certified beds · Last Life Safety survey February 26, 2026

CMS Certification Number 065223 · first certified January 1986

Ownership

Operated by LIFE CARE CENTERS OF AMERICA · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

44
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
24
Inspection & testing records
Of the citations on file

Position within CO

44 citations — more than 99% of the 210 certified nursing homes in CO. Compared within CO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 15. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 10 months from now. This facility’s last Life Safety survey was February 2026. Facilities in CO are typically surveyed 17–24 months after the last one (median 19), measured over 177 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BERKLEY MANOR CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0923 Have enough outside ventilation via a window or mechanical ventilation, or both.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in CO, and nationally. Surveyors differ markedly between states, so the CO figure is the meaningful one.

This facility44CO median16National median11
Citations on file over three years, compared
MeasureCitations
This facility44
Median facility in CO16
Median facility nationally11

Survey history

Citations at each Life Safety survey
122022-08182023-11142026-02
Citations at each Life Safety survey
Survey dateCitations
August 11, 202212
November 30, 202318
February 26, 202614

Most-cited tags

Most-cited tags at this facility
K-03533K-03453K-07123K-03213K-09183K-05112K-02932K-03632
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-02-26
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-02-26
K-0712Have simulated fire drills held at unexpected times.32026-02-26
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-02-26
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-02-26
K-0511Have properly installed electrical wiring and gas equipment.22026-02-26
K-0293Have properly located and lighted "Exit" signs.22026-02-26
K-0363Install corridor and hallway doors that block smoke.22023-11-30

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Gas, Vacuum, and Electrical Systems Deficiencies 11
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 4
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Gas, Vacuum, and Electrical Systems Deficiencies11
Egress Deficiencies7
Miscellaneous Deficiencies4
Services Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 26, 2026 — 14 citations

Citations issued on February 26, 2026
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 12, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 12, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 12, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 12, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 12, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 12, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has plan of correction (July 10, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (April 12, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 12, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (April 12, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 12, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 12, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 12, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 12, 2026)

November 30, 2023 — 18 citations

Citations issued on November 30, 2023
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 13, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (March 13, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 13, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted (May 8, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 13, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (May 8, 2024)
K-0351Install an approved automatic sprinkler system.Waiver has been granted (May 8, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 13, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 13, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 13, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 13, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (May 8, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 13, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (March 13, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (March 13, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Waiver has been granted (May 8, 2024)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (March 13, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 13, 2024)

August 11, 2022 — 12 citations

Citations issued on August 11, 2022
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 21, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 21, 2022)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (September 15, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 21, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 21, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 1, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 1, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 21, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 21, 2022)
K-0917Ensure electrical receptacles or cover plates have distinctive color or marking.Deficient, Provider has date of correction (October 21, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 3, 2022)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (October 21, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.