Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BROADVIEW HEALTH AND REHABILITATION CENTER

GREELEY, CO · 100 certified beds · Last Life Safety survey February 15, 2024

CMS Certification Number 065219 · first certified September 1985

Ownership

Operated by THE ENSIGN GROUP · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

30
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within CO

30 citations — more than 90% of the 210 certified nursing homes in CO. Compared within CO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 5 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (July 2025 to February 2026), and past the point by which nine in ten CO facilities have been surveyed. This facility’s last Life Safety survey was February 2024. Facilities in CO are typically surveyed 17–24 months after the last one (median 19), measured over 177 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BROADVIEW HEALTH AND REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in CO, and nationally. Surveyors differ markedly between states, so the CO figure is the meaningful one.

This facility30CO median16National median11
Citations on file over three years, compared
MeasureCitations
This facility30
Median facility in CO16
Median facility nationally11

Survey history

Citations at each Life Safety survey
102021-08152022-1152024-02
Citations at each Life Safety survey
Survey dateCitations
August 5, 202110
November 17, 202215
February 15, 20245

Most-cited tags

Most-cited tags at this facility
K-03453K-05213K-03532K-09182K-03212K-03242K-03722K-02112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32024-02-15
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.32024-02-15
K-0353Inspect, test, and maintain automatic sprinkler systems.22022-11-17
K-0918Have generator or other power source capable of supplying service within 10 seconds.22022-11-17
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-02-15
K-0324Provide properly protected cooking facilities.22022-11-17
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22022-11-17
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22022-11-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Miscellaneous Deficiencies 4
  • Services Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies5
Miscellaneous Deficiencies4
Services Deficiencies4
Egress Deficiencies4
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 15, 2024 — 5 citations

Citations issued on February 15, 2024
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 15, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 19, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (June 19, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 9, 2024)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Waiver has been granted (April 27, 2024)

November 17, 2022 — 15 citations

Citations issued on November 17, 2022
TagWhat the surveyor checksStatus
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (January 15, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (January 15, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (January 15, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 15, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 15, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (September 30, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 15, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 15, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (January 15, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (January 15, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 15, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 15, 2023)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (January 15, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 15, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 15, 2023)

August 5, 2021 — 10 citations

Citations issued on August 5, 2021
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 20, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 20, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 30, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 30, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 20, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 20, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 20, 2021)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (September 18, 2021)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (August 22, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 30, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.