Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CHERRELYN HEALTHCARE CENTER

LITTLETON, CO · 190 certified beds · Last Life Safety survey January 30, 2025

CMS Certification Number 065203 · first certified December 1984

Ownership

Operated by STELLAR SENIOR LIVING · For profit - Corporation

  • Ownership changed January 1, 2020 (change of ownership)from FIVE STAR QUALITY CARE-COLORADO LLC
37
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within CO

37 citations — more than 95% of the 210 certified nursing homes in CO. Compared within CO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 8 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: July 2026 to February 2027. This facility’s last Life Safety survey was January 2025. Facilities in CO are typically surveyed 17–24 months after the last one (median 19), measured over 177 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CHERRELYN HEALTHCARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 37 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 37 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in CO, and nationally. Surveyors differ markedly between states, so the CO figure is the meaningful one.

This facility37CO median16National median11
Citations on file over three years, compared
MeasureCitations
This facility37
Median facility in CO16
Median facility nationally11

Survey history

Citations at each Life Safety survey
182022-06112023-0882025-01
Citations at each Life Safety survey
Survey dateCitations
June 15, 202218
August 16, 202311
January 30, 20258

Most-cited tags

Most-cited tags at this facility
K-03533K-03243K-03453K-02222K-09182K-03632K-03722K-02912
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-01-30
K-0324Provide properly protected cooking facilities.32025-01-30
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-01-30
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-01-30
K-0918Have generator or other power source capable of supplying service within 10 seconds.22023-08-16
K-0363Install corridor and hallway doors that block smoke.22025-01-30
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22025-01-30
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-01-30

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Egress Deficiencies 7
  • Services Deficiencies 5
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Egress Deficiencies7
Services Deficiencies5
Gas, Vacuum, and Electrical Systems Deficiencies4
Miscellaneous Deficiencies4
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 30, 2025 — 8 citations

Citations issued on January 30, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Waiver has been granted (August 30, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 1, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 15, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (August 30, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (August 30, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 1, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 15, 2025)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (April 1, 2025)

August 16, 2023 — 11 citations

Citations issued on August 16, 2023
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (September 27, 2023)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (November 15, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 15, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 15, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 15, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 15, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 15, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (February 29, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Waiver has been granted (February 29, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (November 15, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 15, 2023)

June 15, 2022 — 18 citations

Citations issued on June 15, 2022
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (July 15, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 25, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 24, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 25, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 14, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 24, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 24, 2022)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 24, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 24, 2022)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (August 24, 2022)
K-0522Have an externally vented heating system.Deficient, Provider has date of correction (July 25, 2022)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (August 24, 2022)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (July 15, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (July 25, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 25, 2022)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (July 25, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 24, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 24, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.