Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

THE LODGE AT RED ROCKS

MORRISON, CO · 180 certified beds · Last Life Safety survey January 15, 2026

CMS Certification Number 065188 · first certified April 1982

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

  • Ownership changed April 5, 2022 (change of ownership)to BEAR CREEK CENTER from PEAK MEDICAL COLORADO NO. 3, LLC
41
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
21
Inspection & testing records
Of the citations on file

Position within CO

41 citations — more than 99% of the 210 certified nursing homes in CO. Compared within CO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 15.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 9 months from now. This facility’s last Life Safety survey was January 2026. Facilities in CO are typically surveyed 17–24 months after the last one (median 19), measured over 177 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about THE LODGE AT RED ROCKS

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 41 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0908 Keep all essential equipment working safely.

How that compares

Citations on file over three years

Compared with the median facility in CO, and nationally. Surveyors differ markedly between states, so the CO figure is the meaningful one.

This facility41CO median16National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in CO16
Median facility nationally11

Survey history

Citations at each Life Safety survey
102019-09212023-09102026-01
Citations at each Life Safety survey
Survey dateCitations
September 25, 201910
September 21, 202321
January 15, 202610

Most-cited tags

Most-cited tags at this facility
K-03243K-03533K-07123K-05212K-03632K-03212K-03452K-03411
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0324Provide properly protected cooking facilities.32026-01-15
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-01-15
K-0712Have simulated fire drills held at unexpected times.32026-01-15
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22023-09-21
K-0363Install corridor and hallway doors that block smoke.22023-09-21
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22023-09-21
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22023-09-21
K-0341Install a fire alarm system that can be heard throughout the facility.12026-01-15

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 17
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Services Deficiencies 6
  • Egress Deficiencies 4
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies17
Gas, Vacuum, and Electrical Systems Deficiencies7
Services Deficiencies6
Egress Deficiencies4
Miscellaneous Deficiencies4
Emergency Preparedness Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 15, 2026 — 10 citations

Citations issued on January 15, 2026
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 29, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 7, 2026)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (April 30, 2026)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (February 25, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 7, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (February 25, 2026)
K-0522Have an externally vented heating system.Deficient, Provider has date of correction (July 7, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 19, 2026)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (April 29, 2026)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (April 29, 2026)

September 21, 2023 — 21 citations

Citations issued on September 21, 2023
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (October 20, 2023)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (October 20, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 13, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 30, 2023)
K-0293Have properly located and lighted "Exit" signs.Waiver has been granted (November 30, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted (January 30, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 30, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (May 29, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (November 29, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Waiver has been granted (November 30, 2023)
K-0363Install corridor and hallway doors that block smoke.Waiver has been granted (May 29, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 30, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 30, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (May 29, 2024)
K-0532Have a properly installed and maintained dumbwaiter or escalator.Waiver has been granted (May 29, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Waiver has been granted (May 29, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 30, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Waiver has been granted (May 29, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (November 30, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 30, 2023)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (November 30, 2023)

September 25, 2019 — 10 citations

Citations issued on September 25, 2019
TagWhat the surveyor checksStatus
K-0271Have exits that are accessible at all times.Waiver has been granted (May 6, 2020)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 25, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 23, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (January 31, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (February 6, 2020)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 9, 2019)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (January 31, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 29, 2019)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (October 25, 2019)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (December 9, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.