Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WESTSIDE CARE CENTER

MANCHESTER, CT · 162 certified beds · Last Life Safety survey June 22, 2026

CMS Certification Number 075252 · first certified March 1976

Ownership

Operated by ICARE HEALTH NETWORK · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

38
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within CT

38 citations — more than 100% of the 191 certified nursing homes in CT. Compared within CT rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens April 2028 — about 18 months from now. This facility’s last Life Safety survey was June 2026. Facilities in CT are typically surveyed 21–28 months after the last one (median 24), measured over 181 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WESTSIDE CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in CT, and nationally. Surveyors differ markedly between states, so the CT figure is the meaningful one.

This facility38CT median10National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in CT10
Median facility nationally11

Survey history

Citations at each Life Safety survey
202022-0482024-11102026-06
Citations at each Life Safety survey
Survey dateCitations
April 19, 202220
November 6, 20248
June 22, 202610

Most-cited tags

Most-cited tags at this facility
K-03633K-09272E-00132K-02912K-03442K-09142K-09182K-03552
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.32026-06-22
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.22026-06-22
E-0013Develop Emergency Preparedness policies and procedures.22024-11-06
K-0291Install emergency lighting that can last at least 1 1/2 hours.22024-11-06
K-0344Have an alternate power supply for its alarm system.22024-11-06
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22024-11-06
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-06-22
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22026-06-22

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 11
  • Egress Deficiencies 4
  • Miscellaneous Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies11
Egress Deficiencies4
Miscellaneous Deficiencies4
Emergency Preparedness Deficiencies3
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 22, 2026 — 10 citations

Citations issued on June 22, 2026
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has no plan of correction
K-0324Provide properly protected cooking facilities.Deficient, Provider has no plan of correction
K-0351Install an approved automatic sprinkler system.Deficient, Provider has no plan of correction
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has no plan of correction
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has no plan of correction
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has no plan of correction
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has no plan of correction
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has no plan of correction
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has no plan of correction
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has no plan of correction

November 6, 2024 — 8 citations

Citations issued on November 6, 2024
TagWhat the surveyor checksStatus
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (December 13, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 13, 2024)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (December 13, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 10, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (December 13, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (December 13, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 13, 2024)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (December 13, 2024)

April 19, 2022 — 20 citations

Citations issued on April 19, 2022
TagWhat the surveyor checksStatus
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (June 16, 2022)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (June 16, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 16, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 16, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 16, 2022)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (June 15, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 16, 2022)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (June 16, 2022)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (June 16, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 16, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 16, 2022)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 16, 2022)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (June 16, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (June 16, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 16, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 16, 2022)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (June 16, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 16, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 16, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 16, 2022)