Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Eastern Star Masonic Home

Boone, IA · 76 certified beds · Last Life Safety survey May 21, 2026

CMS Certification Number 165468 · first certified September 2002

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Other

No change of ownership on CMS record since January 1, 2016, when the records begin.

16
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
7
Inspection & testing records
Of the citations on file

Position within IA

16 citations — more than 70% of the 387 certified nursing homes in IA. Compared within IA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens April 2027 — about 6 months from now. This facility’s last Life Safety survey was May 2026. Facilities in IA are typically surveyed 11–13 months after the last one (median 12), measured over 700 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Eastern Star Masonic Home

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 16 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in IA, and nationally. Surveyors differ markedly between states, so the IA figure is the meaningful one.

This facility16IA median12National median11
Citations on file over three years, compared
MeasureCitations
This facility16
Median facility in IA12
Median facility nationally11

Survey history

Citations at each Life Safety survey
32024-0772025-0462026-05
Citations at each Life Safety survey
Survey dateCitations
July 18, 20243
April 24, 20257
May 21, 20266

Most-cited tags

Most-cited tags at this facility
K-03412K-09182K-09202K-07122K-03742K-03541K-09141K-03451
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0341Install a fire alarm system that can be heard throughout the facility.22025-04-24
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-05-21
K-0920Ensure proper usage of power strips and extension cords.22026-05-21
K-0712Have simulated fire drills held at unexpected times.22026-05-21
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22026-05-21
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.12025-04-24
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.12026-05-21
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12025-04-24

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Miscellaneous Deficiencies 2
  • Egress Deficiencies 2
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies5
Miscellaneous Deficiencies2
Egress Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 21, 2026 — 6 citations

Citations issued on May 21, 2026
TagWhat the surveyor checksStatus
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 21, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 21, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 21, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (May 21, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 3, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 21, 2026)

April 24, 2025 — 7 citations

Citations issued on April 24, 2025
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 5, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (May 23, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 19, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (May 23, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 23, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 14, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 23, 2025)

July 18, 2024 — 3 citations

Citations issued on July 18, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 9, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (August 19, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (July 26, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.