Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Martin Health Center, INC

Cedar Falls, IA · 50 certified beds · Last Life Safety survey May 15, 2025

CMS Certification Number 165508 · first certified December 2003

Ownership

Operated by WESTERN HOME COMMUNITIES · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

17
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
4
Inspection & testing records
Of the citations on file

Position within IA

17 citations — more than 74% of the 387 certified nursing homes in IA. Compared within IA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 7. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (April 2026 to June 2026), and past the point by which nine in ten IA facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in IA are typically surveyed 11–13 months after the last one (median 12), measured over 700 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Martin Health Center, INC

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 17 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in IA, and nationally. Surveyors differ markedly between states, so the IA figure is the meaningful one.

This facility17IA median12National median11
Citations on file over three years, compared
MeasureCitations
This facility17
Median facility in IA12
Median facility nationally11

Survey history

Citations at each Life Safety survey
62023-0682024-0732025-05
Citations at each Life Safety survey
Survey dateCitations
June 15, 20236
July 11, 20248
May 15, 20253

Most-cited tags

Most-cited tags at this facility
K-09202K-07122K-01611K-07411K-03411K-03211K-02931K-09181
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.22025-05-15
K-0712Have simulated fire drills held at unexpected times.22025-05-15
K-0161Use approved construction type or materials.12023-06-15
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.12024-07-11
K-0341Install a fire alarm system that can be heard throughout the facility.12024-07-11
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12024-07-11
K-0293Have properly located and lighted "Exit" signs.12023-06-15
K-0918Have generator or other power source capable of supplying service within 10 seconds.12023-06-15

What the citations cover

Citations by CMS category
  • Miscellaneous Deficiencies 6
  • Smoke Deficiencies 4
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Egress Deficiencies 2
  • Other 1
Citations by CMS category
CategoryCitations
Miscellaneous Deficiencies6
Smoke Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies4
Egress Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 15, 2025 — 3 citations

Citations issued on May 15, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 20, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 19, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 19, 2025)

July 11, 2024 — 8 citations

Citations issued on July 11, 2024
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 16, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 24, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (July 22, 2024)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (July 22, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 31, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 8, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (July 31, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 22, 2024)

June 15, 2023 — 6 citations

Citations issued on June 15, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 18, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 18, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (July 17, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 12, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 19, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 18, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.