Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Accura Healthcare of Toledo

Toledo, IA · 55 certified beds · Last Life Safety survey January 8, 2026

CMS Certification Number 165450 · first certified April 2002

Ownership

Operated by ACCURA HEALTHCARE · For profit - Corporation

  • New ownershipOwnership changed February 1, 2025 (change of ownership)from PREMIER ESTATES OF TOLEDO, LLC
20
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
4
Tags cited more than once
Across separate surveys
12
Inspection & testing records
Of the citations on file

Position within IA

20 citations — more than 85% of the 387 certified nursing homes in IA. Compared within IA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 7. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 2 months from now. This facility’s last Life Safety survey was January 2026. Facilities in IA are typically surveyed 11–13 months after the last one (median 12), measured over 700 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Accura Healthcare of Toledo

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 20 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 20 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in IA, and nationally. Surveyors differ markedly between states, so the IA figure is the meaningful one.

This facility20IA median12National median11
Citations on file over three years, compared
MeasureCitations
This facility20
Median facility in IA12
Median facility nationally11

Survey history

Citations at each Life Safety survey
92023-1252024-1162026-01
Citations at each Life Safety survey
Survey dateCitations
December 12, 20239
November 21, 20245
January 8, 20266

Most-cited tags

Most-cited tags at this facility
K-09183K-09232K-03452K-02912K-03631K-02221K-03471K-09201
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-01-08
K-0923Have proper medical gas storage and administration areas.22026-01-08
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22024-11-21
K-0291Install emergency lighting that can last at least 1 1/2 hours.22024-11-21
K-0363Install corridor and hallway doors that block smoke.12024-11-21
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12023-12-12
K-0347Properly provide smoke detection systems in areas open to corridors.12023-12-12
K-0920Ensure proper usage of power strips and extension cords.12024-11-21

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Smoke Deficiencies 6
  • Egress Deficiencies 4
  • Services Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies7
Smoke Deficiencies6
Egress Deficiencies4
Services Deficiencies1
Emergency Preparedness Deficiencies1
Miscellaneous Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 8, 2026 — 6 citations

Citations issued on January 8, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (January 15, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (January 7, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 15, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 19, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 19, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 7, 2026)

November 21, 2024 — 5 citations

Citations issued on November 21, 2024
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 26, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 25, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 2, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 4, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 2, 2024)

December 12, 2023 — 9 citations

Citations issued on December 12, 2023
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 29, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 12, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 16, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 16, 2023)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (December 16, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (December 13, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 12, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (January 3, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (December 12, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.