Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Landmark at 95th Rehabilitation and Nursing Center

CHICAGO, IL · 228 certified beds · Last Life Safety survey July 24, 2025

CMS Certification Number 145914 · first certified October 1996

Ownership

Operated by INFINITY HEALTHCARE CONSULTING · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

47
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
17
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within IL

47 citations — more than 96% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 18 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (June 2026 to September 2026). Most IL facilities have been surveyed by October 2026. This facility’s last Life Safety survey was July 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Landmark at 95th Rehabilitation and Nursing Center

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 47 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

21 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index

  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility47IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility47
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
82023-06212024-07182025-07
Citations at each Life Safety survey
Survey dateCitations
June 9, 20238
July 17, 202421
July 24, 202518

Most-cited tags

Most-cited tags at this facility
K-09183K-03513K-01613K-03533E-00392K-02222K-03742K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-07-24
K-0351Install an approved automatic sprinkler system.32025-07-24
K-0161Use approved construction type or materials.32025-07-24
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-07-24
E-0039Conduct testing and exercise requirements.22025-07-24
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-07-24
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22025-07-24
K-0324Provide properly protected cooking facilities.22025-07-24

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 21
  • Egress Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Emergency Preparedness Deficiencies 5
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies21
Egress Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies6
Emergency Preparedness Deficiencies5
Miscellaneous Deficiencies3
Construction Deficiencies3
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 24, 2025 — 18 citations

Citations issued on July 24, 2025
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 20, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 20, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 20, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 20, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 20, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 20, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 20, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 20, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction (August 20, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 20, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 20, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 20, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 20, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 20, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (August 20, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 20, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 20, 2025)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (August 20, 2025)

July 17, 2024 — 21 citations

Citations issued on July 17, 2024
TagWhat the surveyor checksStatus
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (August 6, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 6, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 23, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 6, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 6, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 6, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 7, 2024)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 7, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 13, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 7, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 7, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 7, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 7, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 7, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 7, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Waiver has been granted (October 3, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 7, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 7, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 7, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 9, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 7, 2024)

June 9, 2023 — 8 citations

Citations issued on June 9, 2023
TagWhat the surveyor checksStatus
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (July 20, 2023)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 20, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 20, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 20, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (July 20, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 14, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 20, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 20, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.