Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
THE PEARL OF DOWNERS GROVE
DOWNERS GROVE, IL · 145 certified beds · Last Life Safety survey April 14, 2025
CMS Certification Number 145657 · first certified August 1989
Ownership
Operated by PEARL HEALTHCARE · For profit - Corporation
- New ownershipOwnership changed April 10, 2025 (change of ownership)from DOWNERS GROVE SNF OPERATIONS LLC
Position within IL
30 citations — more than 82% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 5 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was April 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about THE PEARL OF DOWNERS GROVE
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
9 of the 30 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 30 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 1, 2023 | 15 |
| February 2, 2024 | 10 |
| April 14, 2025 | 5 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-04-14 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-04-14 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 3 | 2025-04-14 |
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-04-14 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2024-02-02 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2024-02-02 |
| E-0041 | Implement emergency and standby power systems. | 1 | 2023-03-01 |
| K-0133 | Install a two-hour-resistant firewall separation. | 1 | 2023-03-01 |
What the citations cover
- Emergency Preparedness Deficiencies 9
- Smoke Deficiencies 6
- Egress Deficiencies 6
- Miscellaneous Deficiencies 4
- Other 5
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 9 |
| Smoke Deficiencies | 6 |
| Egress Deficiencies | 6 |
| Miscellaneous Deficiencies | 4 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 3 |
| Services Deficiencies | 1 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 14, 2025 — 5 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (April 28, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (April 29, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (April 28, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 29, 2025) |
February 2, 2024 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (March 12, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (March 12, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (March 12, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (February 22, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (February 22, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 23, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 12, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (February 22, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (February 28, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 23, 2024) |
March 1, 2023 — 15 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (April 14, 2023) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (April 14, 2023) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (April 14, 2023) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (April 14, 2023) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (April 14, 2023) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (April 14, 2023) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 12, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (April 14, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 14, 2023) |