Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
APERION CARE FOX RIVER
ELGIN, IL · 94 certified beds · Last Life Safety survey June 25, 2026
CMS Certification Number 145447 · first certified July 1982
Ownership
Operated by APERION CARE · For profit - Corporation
- Ownership changed July 1, 2023 (change of ownership)from HERITAGE MANOR ELGIN LLC
Position within IL
45 citations — more than 95% of the 664 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 11 citations; the earlier surveys on file averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens May 2027 — about 6 months from now. This facility’s last Life Safety survey was June 2026. Facilities in IL are typically surveyed 11–14 months after the last one (median 13), measured over 739 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured
Get an email about APERION CARE FOX RIVER
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
11 of the 45 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 45 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 45 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 17, 2024 | 23 |
| March 13, 2025 | 11 |
| June 25, 2026 | 11 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 3 | 2026-06-25 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3 | 2026-06-25 |
| K-0133 | Install a two-hour-resistant firewall separation. | 3 | 2026-06-25 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2026-06-25 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 2 | 2026-06-25 |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | 2 | 2026-06-25 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-03-13 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2026-06-25 |
What the citations cover
- Smoke Deficiencies 13
- Emergency Preparedness Deficiencies 11
- Egress Deficiencies 8
- Gas, Vacuum, and Electrical Systems Deficiencies 5
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 13 |
| Emergency Preparedness Deficiencies | 11 |
| Egress Deficiencies | 8 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 5 |
| Miscellaneous Deficiencies | 5 |
| Construction Deficiencies | 3 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
June 25, 2026 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 1, 2026) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (July 20, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 22, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (July 21, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (July 20, 2026) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 20, 2026) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (July 1, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 10, 2026) |
March 13, 2025 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (April 2, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 31, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (March 31, 2025) |
May 17, 2024 — 23 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (June 13, 2024) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (May 23, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (June 14, 2024) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (May 22, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (May 24, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (May 23, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 25, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (May 23, 2024) |
Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.