Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Pearl Pointe Nursing Rehab & Care

FREEPORT, IL · 109 certified beds · Last Life Safety survey November 14, 2024

CMS Certification Number 145234 · first certified January 1972

Ownership

Operated by SABA HEALTHCARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

15
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
5
Inspection & testing records
Of the citations on file

Position within IL

15 citations — more than 50% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 6. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (October 2025 to December 2025), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was November 2024. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Pearl Pointe Nursing Rehab & Care

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 15 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 15 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility15IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility15
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
62023-0362023-1232024-11
Citations at each Life Safety survey
Survey dateCitations
March 9, 20236
December 19, 20236
November 14, 20243

Most-cited tags

Most-cited tags at this facility
K-02812K-03632K-09181K-03411K-03211E-00391K-07411K-09201
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0281Install proper backup exit lighting.22024-11-14
K-0363Install corridor and hallway doors that block smoke.22024-11-14
K-0918Have generator or other power source capable of supplying service within 10 seconds.12023-03-09
K-0341Install a fire alarm system that can be heard throughout the facility.12024-11-14
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12023-03-09
E-0039Conduct testing and exercise requirements.12023-12-19
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.12023-03-09
K-0920Ensure proper usage of power strips and extension cords.12023-12-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 5
  • Egress Deficiencies 3
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Emergency Preparedness Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies5
Egress Deficiencies3
Gas, Vacuum, and Electrical Systems Deficiencies3
Emergency Preparedness Deficiencies2
Miscellaneous Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 14, 2024 — 3 citations

Citations issued on November 14, 2024
TagWhat the surveyor checksStatus
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (December 5, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (December 5, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 5, 2024)

December 19, 2023 — 6 citations

Citations issued on December 19, 2023
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (December 18, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 18, 2023)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (December 18, 2023)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (December 18, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 18, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 18, 2023)

March 9, 2023 — 6 citations

Citations issued on March 9, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 3, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 3, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 3, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 3, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 3, 2023)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (April 3, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.