Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CITADEL AT SAINT BENEDICT

NILES, IL · 99 certified beds · Last Life Safety survey May 29, 2025

CMS Certification Number 145731 · first certified August 1992

Ownership

Operated by CITADEL HEALTHCARE · For profit - Corporation

  • Ownership changed September 3, 2024 (change of ownership)from PRESENCE SENIOR SERVICES CHICAGOLAND
58
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
26
Inspection & testing records
Of the citations on file

Position within IL

58 citations — more than 99% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 21 citations; the earlier surveys in the window averaged 18.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (April 2026 to July 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CITADEL AT SAINT BENEDICT

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 58 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 58 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility58IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility58
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
172023-04202024-05212025-05
Citations at each Life Safety survey
Survey dateCitations
April 6, 202317
May 16, 202420
May 29, 202521

Most-cited tags

Most-cited tags at this facility
K-03243K-02253K-07123K-09183K-03533K-03213K-09232K-05212
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0324Provide properly protected cooking facilities.32025-05-29
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.32025-05-29
K-0712Have simulated fire drills held at unexpected times.32025-05-29
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-05-29
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-05-29
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-05-29
K-0923Have proper medical gas storage and administration areas.22025-05-29
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22024-05-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Egress Deficiencies 9
  • Emergency Preparedness Deficiencies 7
  • Other 13
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Gas, Vacuum, and Electrical Systems Deficiencies9
Egress Deficiencies9
Emergency Preparedness Deficiencies7
Miscellaneous Deficiencies6
Services Deficiencies5
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 29, 2025 — 21 citations

Citations issued on May 29, 2025
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (July 8, 2025)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (July 8, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 8, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 8, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (July 8, 2025)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (July 8, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (July 8, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (July 8, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 8, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 8, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 8, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 8, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 8, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 8, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (July 8, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 8, 2025)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (July 8, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 8, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 8, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 8, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 8, 2025)

May 16, 2024 — 20 citations

Citations issued on May 16, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (June 13, 2024)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (June 13, 2024)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (June 13, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (June 13, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 13, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (June 13, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (June 13, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 13, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 13, 2024)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (June 13, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 13, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 13, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 13, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 13, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (August 30, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 13, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 13, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 13, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 13, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 13, 2024)

April 6, 2023 — 17 citations

Citations issued on April 6, 2023
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (May 8, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (May 8, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 8, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 11, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 8, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 11, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (May 8, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (May 8, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 8, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 8, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 2, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 11, 2023)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (April 11, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 5, 2023)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (May 8, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 8, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (May 8, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.