Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
CITADEL AT CASA SCALABRINI
NORTHLAKE, IL · 229 certified beds · Last Life Safety survey March 21, 2025
CMS Certification Number 145956 · first certified January 1998
Ownership
Operated by CITADEL HEALTHCARE · For profit - Individual
- Ownership changed September 3, 2024 (change of ownership)from PRESENCE SENIOR SERVICES CHICAGOLAND
Position within IL
38 citations — more than 92% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 11 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (February 2026 to May 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about CITADEL AT CASA SCALABRINI
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
2 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 38 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 2, 2023 | 12 |
| January 5, 2024 | 15 |
| March 21, 2025 | 11 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-03-21 |
| K-0133 | Install a two-hour-resistant firewall separation. | 3 | 2025-03-21 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-03-21 |
| K-0271 | Have exits that are accessible at all times. | 2 | 2024-01-05 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2025-03-21 |
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2025-03-21 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2025-03-21 |
| K-0923 | Have proper medical gas storage and administration areas. | 2 | 2025-03-21 |
What the citations cover
- Smoke Deficiencies 15
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Egress Deficiencies 6
- Construction Deficiencies 3
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 15 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Egress Deficiencies | 6 |
| Construction Deficiencies | 3 |
| Services Deficiencies | 3 |
| Miscellaneous Deficiencies | 3 |
| Emergency Preparedness Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 21, 2025 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (May 5, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (May 5, 2025) |
January 5, 2024 — 15 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 29, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (February 29, 2024) |
March 2, 2023 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (March 30, 2023) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 23, 2023) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (April 16, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 5, 2023) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (March 30, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (April 16, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 16, 2023) |