Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Landmark of Oak Lawn Rehabilitation and Nursing Ce

OAK LAWN, IL · 143 certified beds · Last Life Safety survey December 19, 2024

CMS Certification Number 145942 · first certified July 1997

Ownership

Operated by INFINITY HEALTHCARE CONSULTING · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

42
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within IL

42 citations — more than 94% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 17 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (November 2025 to January 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was December 2024. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Landmark of Oak Lawn Rehabilitation and Nursing Ce

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 42 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 42 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility42IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility42
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
142022-09112023-09172024-12
Citations at each Life Safety survey
Survey dateCitations
September 1, 202214
September 22, 202311
December 19, 202417

Most-cited tags

Most-cited tags at this facility
K-03533K-09203K-03243K-02113K-07122K-02222K-02252K-03112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-12-19
K-0920Ensure proper usage of power strips and extension cords.32024-12-19
K-0324Provide properly protected cooking facilities.32024-12-19
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32024-12-19
K-0712Have simulated fire drills held at unexpected times.22023-09-22
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22024-12-19
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.22024-12-19
K-0311Have an enclosure around a vertical opening shaft.22024-12-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Egress Deficiencies 7
  • Services Deficiencies 4
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Gas, Vacuum, and Electrical Systems Deficiencies7
Egress Deficiencies7
Services Deficiencies4
Emergency Preparedness Deficiencies4
Miscellaneous Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

December 19, 2024 — 17 citations

Citations issued on December 19, 2024
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (January 22, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (January 22, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 22, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (January 22, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (January 22, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 22, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 22, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 22, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 22, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 22, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (January 22, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 22, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (January 22, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (January 22, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (January 22, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 22, 2025)
K-0929Ensure precautions for handling oxygen cylinders and equipment are correctly followed.Deficient, Provider has date of correction (January 22, 2025)

September 22, 2023 — 11 citations

Citations issued on September 22, 2023
TagWhat the surveyor checksStatus
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (October 23, 2023)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (October 15, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 25, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 25, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 15, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 15, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 25, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 15, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 25, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 25, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 15, 2023)

September 1, 2022 — 14 citations

Citations issued on September 1, 2022
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (November 7, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 7, 2022)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (November 7, 2022)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (November 7, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 7, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 7, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 7, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (August 18, 2023)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (November 7, 2022)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (November 28, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (November 7, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 7, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 7, 2022)
K-0930Ensure proper storage of liquid oxygen.Deficient, Provider has date of correction (November 7, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.