Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Nexus at Palos

PALOS HILLS, IL · 207 certified beds · Last Life Safety survey May 16, 2025

CMS Certification Number 145650 · first certified August 1989

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

87
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
26
Tags cited more than once
Across separate surveys
25
Inspection & testing records
Of the citations on file

Position within IL

87 citations — more than 100% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 24 citations; the earlier surveys in the window averaged 31.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (April 2026 to June 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Nexus at Palos

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

18 of the 87 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

19 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 87 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility87IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility87
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
352022-11282024-02242025-05
Citations at each Life Safety survey
Survey dateCitations
November 3, 202235
February 16, 202428
May 16, 202524

Most-cited tags

Most-cited tags at this facility
K-03743K-03213K-02933K-03723E-00223K-02223K-03453K-09183
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.32025-05-16
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-05-16
K-0293Have properly located and lighted "Exit" signs.32025-05-16
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32025-05-16
E-0022Establish policies and procedures for sheltering.32025-05-16
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32025-05-16
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-05-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-05-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 25
  • Emergency Preparedness Deficiencies 18
  • Gas, Vacuum, and Electrical Systems Deficiencies 14
  • Egress Deficiencies 11
  • Other 19
Citations by CMS category
CategoryCitations
Smoke Deficiencies25
Emergency Preparedness Deficiencies18
Gas, Vacuum, and Electrical Systems Deficiencies14
Egress Deficiencies11
Miscellaneous Deficiencies10
Construction Deficiencies6
Services Deficiencies2
Electrical Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 16, 2025 — 24 citations

Citations issued on May 16, 2025
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (May 16, 2025)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (May 16, 2025)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (May 16, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (May 16, 2025)
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (May 16, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (May 16, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 16, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 16, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (May 16, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 16, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 16, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 16, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 16, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 16, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 16, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 16, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (May 16, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 16, 2025)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (May 16, 2025)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (May 16, 2025)
K-0915Have proper power supply for life support equipment.Waiver has been granted
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (May 16, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 16, 2025)

February 16, 2024 — 28 citations

Citations issued on February 16, 2024
TagWhat the surveyor checksStatus
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (March 15, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (March 15, 2024)
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (March 15, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 15, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 15, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 15, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (March 15, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (March 15, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 15, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 15, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 15, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 15, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (May 22, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 15, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 15, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 15, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 15, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 15, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 15, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 15, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (March 15, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (March 15, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 15, 2024)
K-0915Have proper power supply for life support equipment.Waiver has been granted (August 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 15, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 15, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (March 15, 2024)
K-0929Ensure precautions for handling oxygen cylinders and equipment are correctly followed.Deficient, Provider has date of correction (March 15, 2024)

November 3, 2022 — 35 citations

Citations issued on November 3, 2022
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (December 14, 2022)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (December 13, 2022)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (December 7, 2022)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (December 7, 2022)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (December 7, 2022)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (December 7, 2022)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (December 13, 2022)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (December 13, 2022)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (December 13, 2022)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (December 13, 2022)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 14, 2022)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (December 14, 2022)
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (December 13, 2022)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 13, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 7, 2022)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (December 7, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (December 12, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 7, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 7, 2022)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (December 7, 2022)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (December 2, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (September 26, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (July 15, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 7, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 14, 2022)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Waiver has been granted (March 17, 2023)
K-0531Have elevators that firefighters can control in the event of a fire.Waiver has been granted (September 7, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (December 7, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 7, 2022)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (December 9, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Waiver has been granted (July 8, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 12, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 7, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (December 7, 2022)
K-0929Ensure precautions for handling oxygen cylinders and equipment are correctly followed.Deficient, Provider has date of correction (December 7, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.