Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
EDEN VISTA PROSPECT HEIGHTS
PROSPECT HEIGHTS, IL · 30 certified beds · Last Life Safety survey August 9, 2024
CMS Certification Number 145852 · first certified October 1995
Ownership
Independently operated (no chain recorded by CMS) · For profit - Corporation
- Ownership changed March 1, 2024 (change of ownership)from S-H OPCO PROSPECT HEIGHTS LLC
Position within IL
55 citations — more than 98% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 7 citations; the earlier surveys in the window averaged 24. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (July 2025 to September 2025), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was August 2024. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about EDEN VISTA PROSPECT HEIGHTS
One email when it happens. No account; stop it any time with one click.
7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
18 of the 55 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 55 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 55 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 19, 2022 | 26 |
| May 18, 2023 | 22 |
| August 9, 2024 | 7 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2024-08-09 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2024-08-09 |
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2024-08-09 |
| E-0041 | Implement emergency and standby power systems. | 2 | 2023-05-18 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2023-05-18 |
| E-0015 | Address subsistence needs for staff and patients. | 2 | 2023-05-18 |
| E-0037 | Establish staff and initial training requirements. | 2 | 2023-05-18 |
| E-0039 | Conduct testing and exercise requirements. | 2 | 2023-05-18 |
What the citations cover
- Emergency Preparedness Deficiencies 18
- Smoke Deficiencies 11
- Miscellaneous Deficiencies 9
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Other 8
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 18 |
| Smoke Deficiencies | 11 |
| Miscellaneous Deficiencies | 9 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Egress Deficiencies | 4 |
| Construction Deficiencies | 3 |
| Services Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
August 9, 2024 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0344 | Have an alternate power supply for its alarm system. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 21, 2024) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (August 21, 2024) |
May 18, 2023 — 22 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (June 5, 2023) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 15, 2023) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Waiver has been granted (July 7, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Waiver has been granted (September 25, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 15, 2023) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 15, 2023) |
August 19, 2022 — 26 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (October 6, 2022) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0133 | Install a two-hour-resistant firewall separation. | Waiver has been granted (February 9, 2023) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (October 21, 2022) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (October 21, 2022) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (October 6, 2022) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (October 6, 2022) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.