Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

LANDMARK OF RICHTON PARK REHAB & NSG CTR

RICHTON PARK, IL · 294 certified beds · Last Life Safety survey March 7, 2025

CMS Certification Number 145424 · first certified April 1981

Ownership

Operated by INFINITY HEALTHCARE CONSULTING · For profit - Limited Liability company

  • Ownership changed January 7, 2019 (change of ownership)to LANDMARK OF RICHTON PARK REHABILITATION AND NURSING CENTER from GLEN SHIRE NURSING & REHABILITATION CENTER, INC.
80
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
24
Tags cited more than once
Across separate surveys
24
Inspection & testing records
Of the citations on file

Position within IL

80 citations — more than 100% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 26 citations; the earlier surveys in the window averaged 27. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (February 2026 to April 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about LANDMARK OF RICHTON PARK REHAB & NSG CTR

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

13 of the 80 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 80 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility80IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility80
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
282023-03262024-05262025-03
Citations at each Life Safety survey
Survey dateCitations
March 16, 202328
May 3, 202426
March 7, 202526

Most-cited tags

Most-cited tags at this facility
K-03743K-03213K-07123K-03243K-02223K-09183K-03533K-05313
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.32025-03-07
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-03-07
K-0712Have simulated fire drills held at unexpected times.32025-03-07
K-0324Provide properly protected cooking facilities.32025-03-07
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32025-03-07
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-03-07
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-03-07
K-0531Have elevators that firefighters can control in the event of a fire.32025-03-07

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 26
  • Gas, Vacuum, and Electrical Systems Deficiencies 13
  • Emergency Preparedness Deficiencies 13
  • Egress Deficiencies 13
  • Other 15
Citations by CMS category
CategoryCitations
Smoke Deficiencies26
Gas, Vacuum, and Electrical Systems Deficiencies13
Emergency Preparedness Deficiencies13
Egress Deficiencies13
Services Deficiencies7
Miscellaneous Deficiencies6
Electrical Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 7, 2025 — 26 citations

Citations issued on March 7, 2025
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (March 27, 2025)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (March 28, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (March 28, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 28, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 28, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 28, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (March 28, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 28, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 28, 2025)
K-0311Have an enclosure around a vertical opening shaft.Fire Safety Evaluation Survey (June 12, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 28, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 28, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (May 9, 2025)
K-0352Properly install and monitor supervisory attachments on automatic sprinkler systems.Deficient, Provider has date of correction (March 28, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 28, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 28, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 28, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 28, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 28, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (March 28, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (March 28, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 28, 2025)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (March 28, 2025)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (March 28, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 28, 2025)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (March 28, 2025)

May 3, 2024 — 26 citations

Citations issued on May 3, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (June 7, 2024)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (June 7, 2024)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (June 7, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (June 7, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (June 28, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 7, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 7, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 7, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 7, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (June 7, 2024)
K-0311Have an enclosure around a vertical opening shaft.Fire Safety Evaluation Survey
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 7, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 7, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 7, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 7, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (June 7, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 7, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 7, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (June 7, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (June 7, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 7, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 7, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 7, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 7, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 7, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 7, 2024)

March 16, 2023 — 28 citations

Citations issued on March 16, 2023
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (April 5, 2023)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (April 5, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (April 5, 2023)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (April 5, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 17, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 17, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (March 17, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 17, 2023)
K-0311Have an enclosure around a vertical opening shaft.Fire Safety Evaluation Survey
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 17, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 17, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 17, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 17, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 15, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 17, 2023)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (April 12, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 17, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 6, 2023)
K-0531Have elevators that firefighters can control in the event of a fire.Waiver has been granted
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (April 6, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 11, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 17, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 12, 2023)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (April 26, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 10, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 6, 2023)
K-0929Ensure precautions for handling oxygen cylinders and equipment are correctly followed.Deficient, Provider has date of correction (April 6, 2023)
K-0930Ensure proper storage of liquid oxygen.Deficient, Provider has date of correction (April 6, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.