Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
LANDMARK OF RICHTON PARK REHAB & NSG CTR
RICHTON PARK, IL · 294 certified beds · Last Life Safety survey March 7, 2025
CMS Certification Number 145424 · first certified April 1981
Ownership
Operated by INFINITY HEALTHCARE CONSULTING · For profit - Limited Liability company
- Ownership changed January 7, 2019 (change of ownership)to LANDMARK OF RICHTON PARK REHABILITATION AND NURSING CENTER from GLEN SHIRE NURSING & REHABILITATION CENTER, INC.
Position within IL
80 citations — more than 100% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 26 citations; the earlier surveys in the window averaged 27. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (February 2026 to April 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about LANDMARK OF RICHTON PARK REHAB & NSG CTR
One email when it happens. No account; stop it any time with one click.
7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
13 of the 80 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 80 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 80 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 16, 2023 | 28 |
| May 3, 2024 | 26 |
| March 7, 2025 | 26 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 3 | 2025-03-07 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 3 | 2025-03-07 |
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-03-07 |
| K-0324 | Provide properly protected cooking facilities. | 3 | 2025-03-07 |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 3 | 2025-03-07 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-03-07 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-03-07 |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | 3 | 2025-03-07 |
What the citations cover
- Smoke Deficiencies 26
- Gas, Vacuum, and Electrical Systems Deficiencies 13
- Emergency Preparedness Deficiencies 13
- Egress Deficiencies 13
- Other 15
| Category | Citations |
|---|---|
| Smoke Deficiencies | 26 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 13 |
| Emergency Preparedness Deficiencies | 13 |
| Egress Deficiencies | 13 |
| Services Deficiencies | 7 |
| Miscellaneous Deficiencies | 6 |
| Electrical Deficiencies | 1 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 7, 2025 — 26 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (March 27, 2025) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (March 28, 2025) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Fire Safety Evaluation Survey (June 12, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Waiver has been granted (May 9, 2025) |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0901 | Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0915 | Have proper power supply for life support equipment. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 28, 2025) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (March 28, 2025) |
May 3, 2024 — 26 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (June 7, 2024) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (June 7, 2024) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (June 7, 2024) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (June 7, 2024) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (June 28, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Fire Safety Evaluation Survey |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 7, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 7, 2024) |
March 16, 2023 — 28 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (April 5, 2023) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (April 5, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (April 5, 2023) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (April 5, 2023) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Fire Safety Evaluation Survey |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 15, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (April 12, 2023) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (April 6, 2023) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Waiver has been granted |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (April 6, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (April 11, 2023) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (March 17, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (April 12, 2023) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (April 26, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 10, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (April 6, 2023) |
| K-0929 | Ensure precautions for handling oxygen cylinders and equipment are correctly followed. | Deficient, Provider has date of correction (April 6, 2023) |
| K-0930 | Ensure proper storage of liquid oxygen. | Deficient, Provider has date of correction (April 6, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.