Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
BRIA OF CHICAGO HEIGHTS
SOUTH CHICAGO HEIGHT, IL · 112 certified beds · Last Life Safety survey May 30, 2025
CMS Certification Number 145898 · first certified August 1996
Ownership
Operated by BRIA HEALTH SERVICES · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within IL
54 citations — more than 98% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 25 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (April 2026 to July 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about BRIA OF CHICAGO HEIGHTS
One email when it happens. No account; stop it any time with one click.
7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
7 of the 54 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 54 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0908 Keep all essential equipment working safely.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
How that compares
Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 54 |
| Median facility in IL | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| January 20, 2023 | 20 |
| April 19, 2024 | 9 |
| May 30, 2025 | 25 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0923 | Have proper medical gas storage and administration areas. | 3 | 2025-05-30 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-05-30 |
| K-0363 | Install corridor and hallway doors that block smoke. | 3 | 2025-05-30 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2025-05-30 |
| K-0351 | Install an approved automatic sprinkler system. | 3 | 2025-05-30 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2025-05-30 |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | 3 | 2025-05-30 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 2 | 2025-05-30 |
What the citations cover
- Smoke Deficiencies 19
- Gas, Vacuum, and Electrical Systems Deficiencies 13
- Emergency Preparedness Deficiencies 7
- Egress Deficiencies 7
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 19 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 13 |
| Emergency Preparedness Deficiencies | 7 |
| Egress Deficiencies | 7 |
| Services Deficiencies | 4 |
| Miscellaneous Deficiencies | 4 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 30, 2025 — 25 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (June 18, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (June 18, 2025) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (June 18, 2025) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (June 18, 2025) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (June 26, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 30, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (June 27, 2025) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 18, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 18, 2025) |
April 19, 2024 — 9 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (May 6, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (May 6, 2024) |
January 20, 2023 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (February 7, 2023) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (February 20, 2023) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (February 20, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (February 20, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (February 7, 2023) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (February 7, 2023) |