Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BRIA OF CHICAGO HEIGHTS

SOUTH CHICAGO HEIGHT, IL · 112 certified beds · Last Life Safety survey May 30, 2025

CMS Certification Number 145898 · first certified August 1996

Ownership

Operated by BRIA HEALTH SERVICES · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

54
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within IL

54 citations — more than 98% of the 666 certified nursing homes in IL. Compared within IL rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 25 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (April 2026 to July 2026), and past the point by which nine in ten IL facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in IL are typically surveyed 11–13 months after the last one (median 12), measured over 759 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BRIA OF CHICAGO HEIGHTS

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 54 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 54 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in IL, and nationally. Surveyors differ markedly between states, so the IL figure is the meaningful one.

This facility54IL median15National median11
Citations on file over three years, compared
MeasureCitations
This facility54
Median facility in IL15
Median facility nationally11

Survey history

Citations at each Life Safety survey
202023-0192024-04252025-05
Citations at each Life Safety survey
Survey dateCitations
January 20, 202320
April 19, 20249
May 30, 202525

Most-cited tags

Most-cited tags at this facility
K-09233K-03533K-03633K-03453K-03513K-09203K-09143K-02912
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0923Have proper medical gas storage and administration areas.32025-05-30
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-05-30
K-0363Install corridor and hallway doors that block smoke.32025-05-30
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-05-30
K-0351Install an approved automatic sprinkler system.32025-05-30
K-0920Ensure proper usage of power strips and extension cords.32025-05-30
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.32025-05-30
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-05-30

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 19
  • Gas, Vacuum, and Electrical Systems Deficiencies 13
  • Emergency Preparedness Deficiencies 7
  • Egress Deficiencies 7
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies19
Gas, Vacuum, and Electrical Systems Deficiencies13
Emergency Preparedness Deficiencies7
Egress Deficiencies7
Services Deficiencies4
Miscellaneous Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 30, 2025 — 25 citations

Citations issued on May 30, 2025
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (June 18, 2025)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (June 18, 2025)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (June 18, 2025)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (June 18, 2025)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (June 18, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 18, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (June 18, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 18, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 18, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (June 26, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 18, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 18, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 30, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 18, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 18, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (June 27, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (June 18, 2025)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (June 18, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (June 18, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 18, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (June 18, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 18, 2025)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (June 18, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 18, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 18, 2025)

April 19, 2024 — 9 citations

Citations issued on April 19, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 6, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 6, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (May 6, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 6, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 6, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 6, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (May 6, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 6, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (May 6, 2024)

January 20, 2023 — 20 citations

Citations issued on January 20, 2023
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (February 7, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (February 7, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (February 7, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (February 7, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 7, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (February 7, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 7, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 20, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (February 20, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 7, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 7, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 20, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 7, 2023)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (February 7, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (February 7, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 7, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 7, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 7, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 7, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 7, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.