Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BELLTOWER HEALTH & REHABILITATION CENTER

GRANGER, IN · 96 certified beds · Last Life Safety survey June 9, 2025

CMS Certification Number 155850 · first certified July 2016

Ownership

Operated by FUNDAMENTAL HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

41
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within IN

41 citations — more than 96% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 24 citations; the earlier surveys in the window averaged 8.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (May 2026 to July 2026), and past the point by which nine in ten IN facilities have been surveyed. This facility’s last Life Safety survey was June 2025. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BELLTOWER HEALTH & REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 41 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility41IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
92023-0882024-07242025-06
Citations at each Life Safety survey
Survey dateCitations
August 14, 20239
July 29, 20248
June 9, 202524

Most-cited tags

Most-cited tags at this facility
K-07813K-03243K-03533E-00412K-02322K-03452K-03552E-00392
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0781Have restrictions on the use of portable space heaters.32025-06-09
K-0324Provide properly protected cooking facilities.32025-06-09
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-06-09
E-0041Implement emergency and standby power systems.22025-06-09
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.22025-06-09
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-06-09
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-06-09
E-0039Conduct testing and exercise requirements.22025-06-09

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Miscellaneous Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Emergency Preparedness Deficiencies 5
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Miscellaneous Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies6
Emergency Preparedness Deficiencies5
Egress Deficiencies5
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 9, 2025 — 24 citations

Citations issued on June 9, 2025
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (September 12, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 12, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 12, 2025)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (September 12, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (September 12, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 1, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 12, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 12, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 12, 2025)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (September 12, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 1, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 1, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 12, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 12, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 12, 2025)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 12, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 12, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 1, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 12, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (September 12, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 1, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 12, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 12, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 30, 2025)

July 29, 2024 — 8 citations

Citations issued on July 29, 2024
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 9, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 9, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 9, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 9, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 9, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (September 9, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 9, 2024)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (September 9, 2024)

August 14, 2023 — 9 citations

Citations issued on August 14, 2023
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 5, 2023)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (December 5, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 11, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 5, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 11, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 5, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 11, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (December 5, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (December 5, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.