Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WATERS OF INDIANAPOLIS, THE

INDIANAPOLIS, IN · 81 certified beds · Last Life Safety survey June 26, 2025

CMS Certification Number 155409 · first certified November 1991

Ownership

Operated by INFINITY HEALTHCARE CONSULTING · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

37
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within IN

37 citations — more than 94% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 13 citations; the earlier surveys in the window averaged 12. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (June 2026 to August 2026), and past the point by which nine in ten IN facilities have been surveyed. This facility’s last Life Safety survey was June 2025. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WATERS OF INDIANAPOLIS, THE

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 37 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 37 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0926 Have policies on smoking.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility37IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility37
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
92023-06152024-06132025-06
Citations at each Life Safety survey
Survey dateCitations
June 16, 20239
June 3, 202415
June 26, 202513

Most-cited tags

Most-cited tags at this facility
K-03242K-01002K-05112K-03212K-05212K-09231E-00041K-09141
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0324Provide properly protected cooking facilities.22025-06-26
K-0100Meet other general requirements.22025-06-26
K-0511Have properly installed electrical wiring and gas equipment.22025-06-26
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-06-03
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22024-06-03
K-0923Have proper medical gas storage and administration areas.12025-06-26
E-0004Develop and maintain an Emergency Preparedness Program (EP).12024-06-03
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.12023-06-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Emergency Preparedness Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 5
  • Other 10
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Emergency Preparedness Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies5
Services Deficiencies5
Egress Deficiencies3
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 26, 2025 — 13 citations

Citations issued on June 26, 2025
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (September 9, 2025)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 9, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 9, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (September 9, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 9, 2025)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 9, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 9, 2025)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (September 9, 2025)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (September 9, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (September 9, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 9, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (September 9, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 9, 2025)

June 3, 2024 — 15 citations

Citations issued on June 3, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 29, 2024)
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (August 29, 2024)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (August 29, 2024)
E-0029Develop a communication plan.Deficient, Provider has date of correction (August 29, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (August 29, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 29, 2024)
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 29, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 6, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 29, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 29, 2024)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (August 29, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 29, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 29, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 29, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 29, 2024)

June 16, 2023 — 9 citations

Citations issued on June 16, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 26, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 26, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 26, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 26, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 26, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (August 26, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 26, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 26, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 26, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.