Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
WATERS OF MARTINSVILLE, THE
MARTINSVILLE, IN · 103 certified beds · Last Life Safety survey September 29, 2025
CMS Certification Number 155183 · first certified January 1979
Ownership
Operated by INFINITY HEALTHCARE CONSULTING · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within IN
36 citations — more than 94% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 6 citations; the earlier surveys in the window averaged 10. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: September 2026 to November 2026. This facility’s last Life Safety survey was September 2025. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about WATERS OF MARTINSVILLE, THE
One email when it happens. No account; stop it any time with one click.
3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
4 of the 36 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 36 Life Safety citations above. The Physical Environment Index
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 36 |
| Median facility in IN | 15 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| July 14, 2023 | 3 |
| September 25, 2023 | 2 |
| August 2, 2024 | 25 |
| September 29, 2025 | 6 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2025-09-29 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 3 | 2025-09-29 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2025-09-29 |
| K-0300 | Meet other general requirements that are deficient. | 2 | 2024-08-02 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2025-09-29 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 1 | 2024-08-02 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 1 | 2024-08-02 |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | 1 | 2024-08-02 |
What the citations cover
- Smoke Deficiencies 8
- Egress Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 7
- Services Deficiencies 5
- Other 9
| Category | Citations |
|---|---|
| Smoke Deficiencies | 8 |
| Egress Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 7 |
| Services Deficiencies | 5 |
| Emergency Preparedness Deficiencies | 4 |
| Miscellaneous Deficiencies | 4 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
September 29, 2025 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (December 21, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (December 21, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | No revisit needed |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (December 21, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (December 21, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (December 21, 2025) |
August 2, 2024 — 25 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (September 5, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (September 5, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0300 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Waiver has been granted (August 14, 2024) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (September 5, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (September 5, 2024) |
September 25, 2023 — 2 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (October 9, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (October 9, 2023) |
July 14, 2023 — 3 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0300 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (August 7, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Waiver has been granted (August 15, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (August 11, 2023) |