Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

MAJESTIC CARE OF SOUTH BEND

SOUTH BEND, IN · 103 certified beds · Last Life Safety survey August 19, 2025

CMS Certification Number 155219 · first certified August 1983

Ownership

Independently operated (no chain recorded by CMS) · For profit - Individual

No change of ownership on CMS record since January 1, 2016, when the records begin.

46
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within IN

46 citations — more than 99% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 24 citations; the earlier surveys in the window averaged 11. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: July 2026 to October 2026. This facility’s last Life Safety survey was August 2025. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about MAJESTIC CARE OF SOUTH BEND

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 46 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 46 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility46IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility46
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
122023-08102024-10242025-08
Citations at each Life Safety survey
Survey dateCitations
August 28, 202312
October 4, 202410
August 19, 202524

Most-cited tags

Most-cited tags at this facility
K-09203K-03243K-03533K-07613E-00392K-07122K-07412K-03632
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.32025-08-19
K-0324Provide properly protected cooking facilities.32025-08-19
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-08-19
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32025-08-19
E-0039Conduct testing and exercise requirements.22025-08-19
K-0712Have simulated fire drills held at unexpected times.22025-08-19
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22025-08-19
K-0363Install corridor and hallway doors that block smoke.22025-08-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Miscellaneous Deficiencies 8
  • Emergency Preparedness Deficiencies 6
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies9
Miscellaneous Deficiencies8
Emergency Preparedness Deficiencies6
Egress Deficiencies6
Services Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 19, 2025 — 24 citations

Citations issued on August 19, 2025
TagWhat the surveyor checksStatus
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (October 3, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 3, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 3, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (October 3, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 3, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 3, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 3, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (October 3, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 3, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 3, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 3, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 3, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 3, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 3, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 3, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 3, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 3, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 3, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 3, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 3, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 3, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 3, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 3, 2025)
K-0927Have proper fire barriers, ventilation and signs for the transfilling of oxygen.Deficient, Provider has date of correction (October 3, 2025)

October 4, 2024 — 10 citations

Citations issued on October 4, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (November 7, 2024)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (November 7, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 7, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 11, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 7, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 7, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 7, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 7, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 7, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 7, 2024)

August 28, 2023 — 12 citations

Citations issued on August 28, 2023
TagWhat the surveyor checksStatus
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 26, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 26, 2023)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 26, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 26, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 26, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 26, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 10, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 10, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (October 26, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 10, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (October 26, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.