Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

TRAILPOINT VILLAGE

SOUTH BEND, IN · 183 certified beds · Last Life Safety survey April 13, 2026

CMS Certification Number 155103 · first certified October 1969

Ownership

Operated by AMERICAN SENIOR COMMUNITIES · Government - County

No change of ownership on CMS record since January 1, 2016, when the records begin.

40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within IN

40 citations — more than 96% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 15 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 6 months from now. This facility’s last Life Safety survey was April 2026. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about TRAILPOINT VILLAGE

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

9 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility40IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
192024-0362025-02152026-04
Citations at each Life Safety survey
Survey dateCitations
March 1, 202419
February 28, 20256
April 13, 202615

Most-cited tags

Most-cited tags at this facility
K-05113K-09182K-03742K-07412K-02812E-00412K-03722K-03212
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0511Have properly installed electrical wiring and gas equipment.32026-04-13
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-04-13
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22026-04-13
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22026-04-13
K-0281Install proper backup exit lighting.22026-04-13
E-0041Implement emergency and standby power systems.22026-04-13
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-04-13
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22026-04-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 9
  • Emergency Preparedness Deficiencies 9
  • Egress Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies9
Emergency Preparedness Deficiencies9
Egress Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies5
Services Deficiencies3
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 13, 2026 — 15 citations

Citations issued on April 13, 2026
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 6, 2026)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 6, 2026)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (June 6, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 6, 2026)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 6, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 6, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 6, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 6, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 6, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 6, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 6, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 6, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (June 6, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 6, 2026)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (June 6, 2026)

February 28, 2025 — 6 citations

Citations issued on February 28, 2025
TagWhat the surveyor checksStatus
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (April 25, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 25, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (April 25, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 25, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 25, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 25, 2025)

March 1, 2024 — 19 citations

Citations issued on March 1, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (May 1, 2024)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (May 1, 2024)
E-0029Develop a communication plan.Deficient, Provider has date of correction (May 1, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (May 1, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (May 1, 2024)
K-0100Meet other general requirements.Deficient, Provider has date of correction (May 1, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 1, 2024)
K-0227Have ramps, exits, fire escape ladders, steps, and areas of refuge that meet safety requirements.Waiver has been granted (July 15, 2024)
K-0271Have exits that are accessible at all times.Waiver has been granted (July 15, 2024)
K-0281Install proper backup exit lighting.Waiver has been granted (July 15, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 1, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (May 1, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 1, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 1, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 1, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 1, 2024)
K-0915Have proper power supply for life support equipment.Waiver has been granted (July 15, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Waiver has been granted (July 15, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 1, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.