Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BRICKYARD HEALTHCARE - LINCOLN HILLS CARE CENTER

TELL CITY, IN · 86 certified beds · Last Life Safety survey April 16, 2026

CMS Certification Number 155384 · first certified September 1991

Ownership

Operated by BRICKYARD HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

41
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within IN

41 citations — more than 96% of the 507 certified nursing homes in IN. Compared within IN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 6 months from now. This facility’s last Life Safety survey was April 2026. Facilities in IN are typically surveyed 11–14 months after the last one (median 13), measured over 883 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BRICKYARD HEALTHCARE - LINCOLN HILLS CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 41 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in IN, and nationally. Surveyors differ markedly between states, so the IN figure is the meaningful one.

This facility41IN median15National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in IN15
Median facility nationally11

Survey history

Citations at each Life Safety survey
182024-04162025-0272026-04
Citations at each Life Safety survey
Survey dateCitations
April 22, 202418
February 21, 202516
April 16, 20267

Most-cited tags

Most-cited tags at this facility
K-03533K-03003K-03242K-05412E-00412K-09182K-07122K-03452
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-04-16
K-0300Meet other general requirements that are deficient.32026-04-16
K-0324Provide properly protected cooking facilities.22025-02-21
K-0541Install properly constructed and protected linen or trash chutes.22026-04-16
E-0041Implement emergency and standby power systems.22026-04-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-04-16
K-0712Have simulated fire drills held at unexpected times.22025-02-21
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-04-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Egress Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Services Deficiencies 4
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Egress Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies5
Services Deficiencies4
Emergency Preparedness Deficiencies4
Miscellaneous Deficiencies3
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 16, 2026 — 7 citations

Citations issued on April 16, 2026
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (May 21, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 21, 2026)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (May 21, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 21, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 21, 2026)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (May 21, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 21, 2026)

February 21, 2025 — 16 citations

Citations issued on February 21, 2025
TagWhat the surveyor checksStatus
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (April 3, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 3, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (April 3, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (April 3, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 3, 2025)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (April 3, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (April 3, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 3, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (April 3, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 3, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (April 3, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 3, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 3, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 3, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 3, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 3, 2025)

April 22, 2024 — 18 citations

Citations issued on April 22, 2024
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (June 13, 2024)
K-0200Meet other general requirements.Deficient, Provider has date of correction (June 13, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 13, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 1, 2024)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 13, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 13, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 13, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 13, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 13, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 13, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 1, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 13, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 13, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 13, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (August 1, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (June 13, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 13, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 13, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.