Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

IGNITE MEDICAL RESORT OVERLAND PARK LLC

OVERLAND PARK, KS · 102 certified beds · Last Life Safety survey July 29, 2026

CMS Certification Number 175183 · first certified March 1989

Ownership

Operated by IGNITE MEDICAL RESORTS · For profit - Limited Liability company

  • Ownership changed August 1, 2024 (change of ownership)from CARONDELET LONG TERM CARE FACILITIES INC
43
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
11
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within KS

43 citations — more than 90% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 15 citations; the earlier surveys on file averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2028 — about 16 months from now. This facility’s last Life Safety survey was July 2026. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 290 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about IGNITE MEDICAL RESORT OVERLAND PARK LLC

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

15 of the 43 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 43 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0908 Keep all essential equipment working safely.

How that compares

Citations in CMS's current file

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility43KS median27National median11
Citations in CMS's current file, compared
MeasureCitations
This facility43
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
52023-03232024-07152026-07
Citations at each Life Safety survey
Survey dateCitations
March 20, 20235
July 17, 202423
July 29, 202615

Most-cited tags

Most-cited tags at this facility
K-03533K-03633K-09142K-09202K-02222E-00232K-07122K-02112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-07-29
K-0363Install corridor and hallway doors that block smoke.32026-07-29
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22024-07-17
K-0920Ensure proper usage of power strips and extension cords.22024-07-17
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22026-07-29
E-0023Establish policies and procedures for medical documentation.22026-07-29
K-0712Have simulated fire drills held at unexpected times.22026-07-29
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22026-07-29

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 15
  • Smoke Deficiencies 11
  • Egress Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 5
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies15
Smoke Deficiencies11
Egress Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies6
Services Deficiencies3
Miscellaneous Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 29, 2026 — 15 citations

Citations issued on July 29, 2026
TagWhat the surveyor checksStatus
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has no plan of correction
E-0030List the names and contact information of those in the facility.Deficient, Provider has no plan of correction
E-0031Provide emergency officials' contact information.Deficient, Provider has no plan of correction
E-0041Implement emergency and standby power systems.Deficient, Provider has no plan of correction
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has no plan of correction
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has no plan of correction
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has no plan of correction
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has no plan of correction
K-0324Provide properly protected cooking facilities.Deficient, Provider has no plan of correction
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has no plan of correction
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has no plan of correction
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has no plan of correction
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has no plan of correction
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has no plan of correction
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has no plan of correction

July 17, 2024 — 23 citations

Citations issued on July 17, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (October 18, 2024)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (October 18, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 18, 2024)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (October 18, 2024)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (October 18, 2024)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (October 18, 2024)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (October 18, 2024)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (October 18, 2024)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (October 18, 2024)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (October 18, 2024)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (October 18, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 18, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 18, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 18, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 18, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 18, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 18, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 18, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 18, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 18, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 18, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 18, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 18, 2024)

March 20, 2023 — 5 citations

Citations issued on March 20, 2023
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 6, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 6, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 6, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 6, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 6, 2023)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.