Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PITTSBURG CARE AND REHAB

PITTSBURG, KS · 86 certified beds · Last Life Safety survey May 29, 2024

CMS Certification Number 175208 · first certified May 1991

Ownership

Operated by MISSION HEALTH COMMUNITIES · For profit - Limited Liability company

  • Ownership changed October 1, 2019 (change of ownership)from PITTSBURG CARE AND REHABILITATION CENTER LLC
40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
21
Inspection & testing records
Of the citations on file

Position within KS

40 citations — more than 85% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (January 2026 to April 2026), and past the point by which nine in ten KS facilities have been surveyed. This facility’s last Life Safety survey was May 2024. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PITTSBURG CARE AND REHAB

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility40KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
142021-03142022-09122024-05
Citations at each Life Safety survey
Survey dateCitations
March 4, 202114
September 15, 202214
May 29, 202412

Most-cited tags

Most-cited tags at this facility
K-03533K-07413K-09203K-05113K-03213K-09183K-07122K-09232
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-05-29
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32024-05-29
K-0920Ensure proper usage of power strips and extension cords.32024-05-29
K-0511Have properly installed electrical wiring and gas equipment.32024-05-29
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-05-29
K-0918Have generator or other power source capable of supplying service within 10 seconds.32024-05-29
K-0712Have simulated fire drills held at unexpected times.22024-05-29
K-0923Have proper medical gas storage and administration areas.22024-05-29

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Miscellaneous Deficiencies 6
  • Services Deficiencies 3
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Gas, Vacuum, and Electrical Systems Deficiencies10
Miscellaneous Deficiencies6
Services Deficiencies3
Egress Deficiencies2
Emergency Preparedness Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 29, 2024 — 12 citations

Citations issued on May 29, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 18, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 18, 2024)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (July 18, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 8, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 18, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 8, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 18, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 8, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 18, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 8, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 18, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 18, 2024)

September 15, 2022 — 14 citations

Citations issued on September 15, 2022
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 17, 2022)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (November 17, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 17, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 17, 2022)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (November 17, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 17, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 17, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 17, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 17, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 17, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 17, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 17, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 17, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 17, 2022)

March 4, 2021 — 14 citations

Citations issued on March 4, 2021
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 21, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 21, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 21, 2021)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (September 21, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 21, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 21, 2021)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 21, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 21, 2021)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 21, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 21, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 21, 2021)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 21, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 21, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 21, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.