Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

ADVENA LIVING AT FOUNTAINVIEW

ROSE HILL, KS · 50 certified beds · Last Life Safety survey January 23, 2025

CMS Certification Number 175221 · first certified April 1992

Ownership

Operated by ADVENA LIVING COMMUNITIES · For profit - Corporation

  • Ownership changed November 1, 2019 (change of ownership)to FOUNTAINVIEW NURSING AND REHAB CENTER from PINNACLE HEALTH FACILITIES XXXV LP
59
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
16
Tags cited more than once
Across separate surveys
26
Inspection & testing records
Of the citations on file

Position within KS

59 citations — more than 99% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 22.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: September 2026 to November 2026. This facility’s last Life Safety survey was January 2025. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about ADVENA LIVING AT FOUNTAINVIEW

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 59 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 59 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility59KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility59
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
152021-06302023-01142025-01
Citations at each Life Safety survey
Survey dateCitations
June 16, 202115
January 23, 202330
January 23, 202514

Most-cited tags

Most-cited tags at this facility
K-03533K-09203K-07413K-07123K-03723K-03633K-09182K-02912
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-01-23
K-0920Ensure proper usage of power strips and extension cords.32025-01-23
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32025-01-23
K-0712Have simulated fire drills held at unexpected times.32025-01-23
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32025-01-23
K-0363Install corridor and hallway doors that block smoke.32025-01-23
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-01-23
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-01-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Miscellaneous Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 8
  • Other 12
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Miscellaneous Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies8
Emergency Preparedness Deficiencies6
Construction Deficiencies3
Services Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 23, 2025 — 14 citations

Citations issued on January 23, 2025
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 7, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 7, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 11, 2025)
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Deficient, Provider has date of correction (February 5, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 10, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 7, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 7, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 7, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 7, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 7, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 10, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 7, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 7, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 7, 2025)

January 23, 2023 — 30 citations

Citations issued on January 23, 2023
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (July 3, 2023)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (July 3, 2023)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (July 3, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (June 26, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 26, 2023)
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.Deficient, Provider has date of correction (June 26, 2023)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 26, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 26, 2023)
K-0252Provide at least two remote exits on each floor or fire section of the building.Deficient, Provider has date of correction (July 3, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 26, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 26, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 26, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Waiver has been granted (August 30, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 3, 2023)
K-0351Install an approved automatic sprinkler system.Waiver has been granted (September 11, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 26, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (June 26, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 26, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 26, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 26, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 26, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 3, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 28, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 26, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 26, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 3, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (June 26, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 3, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 26, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 26, 2023)

June 16, 2021 — 15 citations

Citations issued on June 16, 2021
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 23, 2021)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 23, 2021)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 23, 2021)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 23, 2021)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 23, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (July 14, 2021)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 23, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 23, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 23, 2021)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (August 23, 2021)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 23, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 23, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 23, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 23, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 23, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.