Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WHEATLAND NURSING & REHABILITATION CENTER

RUSSELL, KS · 45 certified beds · Last Life Safety survey June 26, 2025

CMS Certification Number 175286 · first certified April 1994

Ownership

Operated by AMERICARE SENIOR LIVING · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

20
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
4
Tags cited more than once
Across separate surveys
11
Inspection & testing records
Of the citations on file

Position within KS

20 citations — more than 23% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 5.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens February 2027 — about 5 months from now. This facility’s last Life Safety survey was June 2025. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WHEATLAND NURSING & REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 20 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility20KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility20
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
42022-0472023-1092025-06
Citations at each Life Safety survey
Survey dateCitations
April 5, 20224
October 30, 20237
June 26, 20259

Most-cited tags

Most-cited tags at this facility
K-03213K-09203K-03532K-05112K-03421K-03451K-01611K-03241
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-06-26
K-0920Ensure proper usage of power strips and extension cords.32025-06-26
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-06-26
K-0511Have properly installed electrical wiring and gas equipment.22025-06-26
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.12025-06-26
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12023-10-30
K-0161Use approved construction type or materials.12022-04-05
K-0324Provide properly protected cooking facilities.12025-06-26

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Services Deficiencies 2
  • Miscellaneous Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies4
Services Deficiencies2
Miscellaneous Deficiencies2
Egress Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 26, 2025 — 9 citations

Citations issued on June 26, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 5, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 5, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 21, 2025)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (August 27, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 4, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 22, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 4, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 4, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 18, 2025)

October 30, 2023 — 7 citations

Citations issued on October 30, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 8, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 8, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 8, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 8, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 8, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 8, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 8, 2024)

April 5, 2022 — 4 citations

Citations issued on April 5, 2022
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 14, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 14, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 14, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 14, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.