Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

SHARON LANE HEALTH AND REHABILITATION

SHAWNEE, KS · 78 certified beds · Last Life Safety survey November 17, 2025

CMS Certification Number 175257 · first certified August 1993

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

17
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
4
Tags cited more than once
Across separate surveys
12
Inspection & testing records
Of the citations on file

Position within KS

17 citations — more than 15% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 4. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was November 2025. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about SHARON LANE HEALTH AND REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 17 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility17KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility17
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
32022-0552024-0192025-11
Citations at each Life Safety survey
Survey dateCitations
May 4, 20223
January 31, 20245
November 17, 20259

Most-cited tags

Most-cited tags at this facility
K-03533K-03633K-03452K-09202K-05311K-03721K-02911K-07531
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-17
K-0363Install corridor and hallway doors that block smoke.32025-11-17
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-11-17
K-0920Ensure proper usage of power strips and extension cords.22025-11-17
K-0531Have elevators that firefighters can control in the event of a fire.12025-11-17
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12025-11-17
K-0291Install emergency lighting that can last at least 1 1/2 hours.12022-05-04
K-0753Have restrictions on the use of highly flammable decorations.12025-11-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
  • Miscellaneous Deficiencies 2
  • Services Deficiencies 2
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies3
Miscellaneous Deficiencies2
Services Deficiencies2
Egress Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 17, 2025 — 9 citations

Citations issued on November 17, 2025
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 16, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 16, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 16, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 16, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 16, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (February 16, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 16, 2026)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (February 16, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 16, 2026)

January 31, 2024 — 5 citations

Citations issued on January 31, 2024
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 19, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 19, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 17, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 17, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 19, 2024)

May 4, 2022 — 3 citations

Citations issued on May 4, 2022
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 21, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 21, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 21, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.