Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

SANDPIPER HEALTHCARE & REHABILITATION CENTER

WICHITA, KS · 104 certified beds · Last Life Safety survey November 7, 2024

CMS Certification Number 175344 · first certified May 1995

Ownership

Operated by RECOVER-CARE HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

51
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within KS

51 citations — more than 96% of the 296 certified nursing homes in KS. Compared within KS rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 20 citations; the earlier surveys in the window averaged 10.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (July 2026 to September 2026). Most KS facilities have been surveyed by October 2026. This facility’s last Life Safety survey was November 2024. Facilities in KS are typically surveyed 20–22 months after the last one (median 21), measured over 298 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about SANDPIPER HEALTHCARE & REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 51 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 51 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in KS, and nationally. Surveyors differ markedly between states, so the KS figure is the meaningful one.

This facility51KS median27National median11
Citations on file over three years, compared
MeasureCitations
This facility51
Median facility in KS27
Median facility nationally11

Survey history

Citations at each Life Safety survey
122021-02162023-0132024-07202024-11
Citations at each Life Safety survey
Survey dateCitations
February 4, 202112
January 5, 202316
July 31, 20243
November 7, 202420

Most-cited tags

Most-cited tags at this facility
K-03453K-03533K-07123K-09203K-03633K-03722K-02222K-01612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32024-11-07
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-11-07
K-0712Have simulated fire drills held at unexpected times.32024-11-07
K-0920Ensure proper usage of power strips and extension cords.32024-11-07
K-0363Install corridor and hallway doors that block smoke.32024-11-07
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-11-07
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22024-11-07
K-0161Use approved construction type or materials.22024-11-07

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Emergency Preparedness Deficiencies 7
  • Miscellaneous Deficiencies 7
  • Other 10
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Gas, Vacuum, and Electrical Systems Deficiencies7
Emergency Preparedness Deficiencies7
Miscellaneous Deficiencies7
Egress Deficiencies5
Construction Deficiencies3
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 7, 2024 — 20 citations

Citations issued on November 7, 2024
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (December 12, 2024)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (December 12, 2024)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (December 12, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (December 12, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 18, 2024)
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (December 12, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 18, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 12, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 19, 2024)
K-0251Conform to length requirements for dead end corridors.Deficient, Provider has date of correction (December 12, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 12, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 18, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 12, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 19, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 12, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 18, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 18, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 12, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 12, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 18, 2024)

July 31, 2024 — 3 citations

Citations issued on July 31, 2024
TagWhat the surveyor checksStatus
E-0001Establish an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 8, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 8, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 8, 2024)

January 5, 2023 — 16 citations

Citations issued on January 5, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 10, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 10, 2023)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (March 10, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 10, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 10, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (March 10, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 10, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 10, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 10, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 10, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 10, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 10, 2023)
K-0771Ensure that smoke control systems are tested and documented in accordance with established engineering principles.Deficient, Provider has date of correction (March 10, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 10, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 10, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 10, 2023)

February 4, 2021 — 12 citations

Citations issued on February 4, 2021
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 15, 2021)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (April 15, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 15, 2021)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (April 15, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 15, 2021)
K-0371Have properly sized and located compartments to protect residents from smoke.Deficient, Provider has date of correction (April 15, 2021)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (April 15, 2021)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 15, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 15, 2021)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 15, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 15, 2021)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 15, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.