Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CONTINUING CARE AT BROOKSBY VILLAGE

PEABODY, MA · 104 certified beds · Last Life Safety survey January 21, 2026

CMS Certification Number 225767 · first certified March 2004

Ownership

Operated by ERICKSON SENIOR LIVING · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

15
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
10
Inspection & testing records
Of the citations on file

Position within MA

15 citations — more than 67% of the 341 certified nursing homes in MA. Compared within MA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 4. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was January 2026. Facilities in MA are typically surveyed 12–15 months after the last one (median 13), measured over 556 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CONTINUING CARE AT BROOKSBY VILLAGE

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 15 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 15 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in MA, and nationally. Surveyors differ markedly between states, so the MA figure is the meaningful one.

This facility15MA median11National median11
Citations on file over three years, compared
MeasureCitations
This facility15
Median facility in MA11
Median facility nationally11

Survey history

Citations at each Life Safety survey
02023-1282024-1272026-01
Citations at each Life Safety survey
Survey dateCitations
December 6, 20230
December 23, 20248
January 21, 20267

Most-cited tags

Most-cited tags at this facility
K-09182K-03532K-03721K-07121K-05211K-02231K-03111E-00411
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-01-21
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-01-21
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12024-12-23
K-0712Have simulated fire drills held at unexpected times.12024-12-23
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.12026-01-21
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.12024-12-23
K-0311Have an enclosure around a vertical opening shaft.12026-01-21
E-0041Implement emergency and standby power systems.12024-12-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 7
  • Egress Deficiencies 2
  • Gas, Vacuum, and Electrical Systems Deficiencies 2
  • Emergency Preparedness Deficiencies 1
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies7
Egress Deficiencies2
Gas, Vacuum, and Electrical Systems Deficiencies2
Emergency Preparedness Deficiencies1
Services Deficiencies1
Miscellaneous Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 21, 2026 — 7 citations

Citations issued on January 21, 2026
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (February 20, 2026)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (April 9, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 9, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 9, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 9, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (February 20, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 20, 2026)

December 23, 2024 — 8 citations

Citations issued on December 23, 2024
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (February 16, 2025)
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (February 16, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (February 16, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 16, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 16, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 16, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 16, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 16, 2025)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.