Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

MARYLAND BAPTIST AGED HOME

BALTIMORE, MD · 29 certified beds · Last Life Safety survey June 17, 2026

CMS Certification Number 215360 · first certified August 2013

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Church related

No change of ownership on CMS record since January 1, 2016, when the records begin.

34
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
9
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within MD

34 citations — more than 81% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 7 citations; the earlier surveys on file averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens October 2027 — about 11 months from now. This facility’s last Life Safety survey was June 2026. Facilities in MD are typically surveyed 16–48 months after the last one (median 23), measured over 307 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about MARYLAND BAPTIST AGED HOME

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 34 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 34 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0924 Put firmly secured handrails on each side of hallways.

How that compares

Citations in CMS's current file

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility34MD median23National median11
Citations in CMS's current file, compared
MeasureCitations
This facility34
Median facility in MD23
Median facility nationally11

Survey history

Citations at each Life Safety survey
182022-0692025-0672026-06
Citations at each Life Safety survey
Survey dateCitations
June 30, 202218
June 2, 20259
June 17, 20267

Most-cited tags

Most-cited tags at this facility
K-03533K-07123K-03452K-09142K-09232K-03472K-09182K-03432
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-06-17
K-0712Have simulated fire drills held at unexpected times.32026-06-17
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-06-02
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22025-06-02
K-0923Have proper medical gas storage and administration areas.22026-06-17
K-0347Properly provide smoke detection systems in areas open to corridors.22025-06-02
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-06-02
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.22026-06-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Miscellaneous Deficiencies 6
  • Emergency Preparedness Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Gas, Vacuum, and Electrical Systems Deficiencies8
Miscellaneous Deficiencies6
Emergency Preparedness Deficiencies2
Egress Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 17, 2026 — 7 citations

Citations issued on June 17, 2026
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 17, 2026)
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Past Non-Compliance (July 13, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 17, 2026)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 17, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 17, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 17, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 17, 2026)

June 2, 2025 — 9 citations

Citations issued on June 2, 2025
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 5, 2025)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (September 5, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 5, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 5, 2025)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (September 5, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 5, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 5, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (September 5, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 5, 2025)

June 30, 2022 — 18 citations

Citations issued on June 30, 2022
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (January 6, 2023)
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (January 6, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 31, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 31, 2022)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (January 6, 2023)
K-0343Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.Deficient, Provider has date of correction (January 6, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 6, 2023)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 31, 2022)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (January 6, 2023)
K-0352Properly install and monitor supervisory attachments on automatic sprinkler systems.Deficient, Provider has date of correction (January 6, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 6, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 31, 2022)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (January 6, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 31, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 31, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 6, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (August 31, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 31, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.