Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
CHESTERTOWN NURSING AND REHAB
CHESTERTOWN, MD · 92 certified beds · Last Life Safety survey September 28, 2023
CMS Certification Number 215260 · first certified September 1994
Ownership
Operated by KEY HEALTH MANAGEMENT · For profit - Limited Liability company
- Ownership changed April 1, 2023 (change of ownership)from CHESTERTOWN MD OPCO LLC
Position within MD
28 citations — more than 68% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 14 citations; the earlier surveys in the window averaged 7. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: March 2025 to August 2028. This facility’s last Life Safety survey was September 2023. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about CHESTERTOWN NURSING AND REHAB
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
1 of the 28 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 28 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 28 |
| Median facility in MD | 22 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| October 19, 2017 | 6 |
| February 15, 2019 | 8 |
| September 28, 2023 | 14 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2023-09-28 |
| K-0324 | Provide properly protected cooking facilities. | 2 | 2023-09-28 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2023-09-28 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2023-09-28 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 2 | 2023-09-28 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 2 | 2023-09-28 |
| K-0200 | Meet other general requirements. | 1 | 2019-02-15 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 1 | 2019-02-15 |
What the citations cover
- Smoke Deficiencies 11
- Egress Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 5
- Miscellaneous Deficiencies 4
- Other 1
| Category | Citations |
|---|---|
| Smoke Deficiencies | 11 |
| Egress Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 5 |
| Miscellaneous Deficiencies | 4 |
| Emergency Preparedness Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
September 28, 2023 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (January 17, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Waiver has been granted (February 12, 2024) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (February 12, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Waiver has been granted (February 12, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Waiver has been granted (February 12, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (January 17, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 12, 2024) |
February 15, 2019 — 8 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0200 | Meet other general requirements. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (June 14, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 14, 2019) |
October 19, 2017 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (January 12, 2018) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (January 7, 2018) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (January 7, 2018) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (January 7, 2018) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (January 12, 2018) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (December 28, 2017) |