Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
FAIRFIELD NURSING & REHABILITATION CENTER
CROWNSVILLE, MD · 96 certified beds · Last Life Safety survey November 21, 2025
CMS Certification Number 215236 · first certified November 1991
Ownership
Operated by FUNDAMENTAL HEALTHCARE · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within MD
47 citations — more than 97% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 10 citations; the earlier surveys in the window averaged 18.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens April 2027 — about 7 months from now. This facility’s last Life Safety survey was November 2025. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about FAIRFIELD NURSING & REHABILITATION CENTER
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
2 of the 47 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
14 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0924 Put firmly secured handrails on each side of hallways.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 47 |
| Median facility in MD | 22 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 3, 2019 | 6 |
| May 3, 2024 | 31 |
| November 21, 2025 | 10 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-11-21 |
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-11-21 |
| K-0293 | Have properly located and lighted "Exit" signs. | 2 | 2024-05-03 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 2 | 2024-05-03 |
| K-0324 | Provide properly protected cooking facilities. | 2 | 2025-11-21 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 2 | 2025-11-21 |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | 2 | 2025-11-21 |
| K-0100 | Meet other general requirements. | 2 | 2025-11-21 |
What the citations cover
- Smoke Deficiencies 14
- Egress Deficiencies 11
- Gas, Vacuum, and Electrical Systems Deficiencies 8
- Services Deficiencies 5
- Other 9
| Category | Citations |
|---|---|
| Smoke Deficiencies | 14 |
| Egress Deficiencies | 11 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 8 |
| Services Deficiencies | 5 |
| Miscellaneous Deficiencies | 5 |
| Emergency Preparedness Deficiencies | 2 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
November 21, 2025 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (June 5, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (May 29, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 5, 2026) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (May 29, 2026) |
May 3, 2024 — 31 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (August 1, 2024) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0200 | Meet other general requirements. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Waiver has been granted (August 28, 2024) |
| K-0251 | Conform to length requirements for dead end corridors. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0261 | Have properly spaced exits within rooms. | Waiver has been granted (August 28, 2024) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Waiver has been granted (August 28, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 9, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0344 | Have an alternate power supply for its alarm system. | Waiver has been granted (August 28, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 28, 2024) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (August 9, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Waiver has been granted (August 28, 2024) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Waiver has been granted (August 28, 2024) |
| K-0525 | Enure that solid fuel-burning fireplaces are not in patient sleeping areas. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (August 9, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (August 1, 2024) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Waiver has been granted (August 28, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Waiver has been granted (August 28, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (August 1, 2024) |
May 3, 2019 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 10, 2019) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (June 10, 2019) |
| K-0522 | Have an externally vented heating system. | Deficient, Provider has date of correction (June 10, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 10, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 10, 2019) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 10, 2019) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.