Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

DENTON NURSING AND REHAB

DENTON, MD · 100 certified beds · Last Life Safety survey March 16, 2026

CMS Certification Number 215149 · first certified April 1984

Ownership

Operated by KEY HEALTH MANAGEMENT · For profit - Limited Liability company

  • Ownership changed April 1, 2023 (change of ownership)from DENTON MD OPCO LLC
47
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
16
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within MD

47 citations — more than 97% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 12.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 11 months from now. This facility’s last Life Safety survey was March 2026. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about DENTON NURSING AND REHAB

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 47 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility47MD median22National median11
Citations on file over three years, compared
MeasureCitations
This facility47
Median facility in MD22
Median facility nationally11

Survey history

Citations at each Life Safety survey
122019-07202024-1152025-01102026-03
Citations at each Life Safety survey
Survey dateCitations
July 26, 201912
November 1, 202420
January 29, 20255
March 16, 202610

Most-cited tags

Most-cited tags at this facility
K-03533K-03453K-09183K-03473K-03623K-07613K-02233K-07122
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-03-16
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-03-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-03-16
K-0347Properly provide smoke detection systems in areas open to corridors.32026-03-16
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.32026-03-16
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32026-03-16
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.32026-03-16
K-0712Have simulated fire drills held at unexpected times.22026-03-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 22
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Egress Deficiencies 6
  • Miscellaneous Deficiencies 5
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies22
Gas, Vacuum, and Electrical Systems Deficiencies9
Egress Deficiencies6
Miscellaneous Deficiencies5
Services Deficiencies4
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 16, 2026 — 10 citations

Citations issued on March 16, 2026
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 11, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 11, 2026)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (June 11, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 11, 2026)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (June 11, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 11, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 11, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 11, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 11, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 11, 2026)

January 29, 2025 — 5 citations

Citations issued on January 29, 2025
TagWhat the surveyor checksStatus
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 27, 2025)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (March 27, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 27, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (March 27, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (March 27, 2025)

November 1, 2024 — 20 citations

Citations issued on November 1, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (February 10, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (February 10, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (February 10, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 10, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted (March 27, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 10, 2025)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (February 10, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 27, 2025)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (March 27, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 27, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (February 10, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (February 10, 2025)
K-0500Meet other general requirements that are deficient.Waiver has been granted (March 27, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 10, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 10, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (March 27, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Waiver has been granted (March 27, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 10, 2025)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (February 10, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 10, 2025)

July 26, 2019 — 12 citations

Citations issued on July 26, 2019
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 21, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 21, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 21, 2019)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 21, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 21, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 21, 2019)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (October 21, 2019)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 21, 2019)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 21, 2019)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (October 21, 2019)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 21, 2019)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (October 21, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.