Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
DENTON NURSING AND REHAB
DENTON, MD · 100 certified beds · Last Life Safety survey March 16, 2026
CMS Certification Number 215149 · first certified April 1984
Ownership
Operated by KEY HEALTH MANAGEMENT · For profit - Limited Liability company
- Ownership changed April 1, 2023 (change of ownership)from DENTON MD OPCO LLC
Position within MD
47 citations — more than 97% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 10 citations; the earlier surveys in the window averaged 12.3. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens August 2027 — about 11 months from now. This facility’s last Life Safety survey was March 2026. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about DENTON NURSING AND REHAB
One email when it happens. No account; stop it any time with one click.
9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
1 of the 47 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
- F-0908 Keep all essential equipment working safely.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 47 |
| Median facility in MD | 22 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| July 26, 2019 | 12 |
| November 1, 2024 | 20 |
| January 29, 2025 | 5 |
| March 16, 2026 | 10 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-03-16 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2026-03-16 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-03-16 |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | 3 | 2026-03-16 |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | 3 | 2026-03-16 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3 | 2026-03-16 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 3 | 2026-03-16 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2026-03-16 |
What the citations cover
- Smoke Deficiencies 22
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Egress Deficiencies 6
- Miscellaneous Deficiencies 5
- Other 5
| Category | Citations |
|---|---|
| Smoke Deficiencies | 22 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Egress Deficiencies | 6 |
| Miscellaneous Deficiencies | 5 |
| Services Deficiencies | 4 |
| Emergency Preparedness Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 16, 2026 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 11, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 11, 2026) |
January 29, 2025 — 5 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (March 27, 2025) |
November 1, 2024 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (February 10, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Waiver has been granted (March 27, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0344 | Have an alternate power supply for its alarm system. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0347 | Properly provide smoke detection systems in areas open to corridors. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0500 | Meet other general requirements that are deficient. | Waiver has been granted (March 27, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (March 27, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Waiver has been granted (March 27, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (February 10, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (February 10, 2025) |
July 26, 2019 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 21, 2019) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (October 21, 2019) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.