Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

AUTUMN LAKE HEALTHCARE AT PIKESVILLE

PIKESVILLE, MD · 140 certified beds · Last Life Safety survey July 31, 2026

CMS Certification Number 215082 · first certified June 1976

Ownership

Operated by AUTUMN LAKE HEALTHCARE · For profit - Limited Liability company

  • Ownership changed August 1, 2018 (change of ownership)from BRINTON WOODS OF PIKESVILLE LLC
39
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
9
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within MD

39 citations — more than 93% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 10 citations; the earlier surveys on file averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2027 — about 12 months from now. This facility’s last Life Safety survey was July 2026. Facilities in MD are typically surveyed 16–48 months after the last one (median 23), measured over 307 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about AUTUMN LAKE HEALTHCARE AT PIKESVILLE

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 39 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 39 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0922 Have enough backup water supply for essential areas of the nursing home.

How that compares

Citations in CMS's current file

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility39MD median23National median11
Citations in CMS's current file, compared
MeasureCitations
This facility39
Median facility in MD23
Median facility nationally11

Survey history

Citations at each Life Safety survey
172022-08122025-06102026-07
Citations at each Life Safety survey
Survey dateCitations
August 11, 202217
June 18, 202512
July 31, 202610

Most-cited tags

Most-cited tags at this facility
K-03533K-03633K-09182K-03742K-03552K-07122K-09232K-07412
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-07-31
K-0363Install corridor and hallway doors that block smoke.32026-07-31
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-06-18
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22026-07-31
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22026-07-31
K-0712Have simulated fire drills held at unexpected times.22026-07-31
K-0923Have proper medical gas storage and administration areas.22026-07-31
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22026-07-31

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Miscellaneous Deficiencies 6
  • Egress Deficiencies 5
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies6
Egress Deficiencies5
Emergency Preparedness Deficiencies4
Services Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 31, 2026 — 10 citations

Citations issued on July 31, 2026
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (September 15, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 15, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 15, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 15, 2026)
K-0371Have properly sized and located compartments to protect residents from smoke.Deficient, Provider has date of correction (September 15, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 15, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 15, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 15, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 15, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 15, 2026)

June 18, 2025 — 12 citations

Citations issued on June 18, 2025
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 29, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 29, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 29, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 29, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 29, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 29, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 29, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 29, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 29, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (August 29, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 29, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 29, 2025)

August 11, 2022 — 17 citations

Citations issued on August 11, 2022
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (August 31, 2022)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (August 31, 2022)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 31, 2022)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 31, 2022)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 31, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 31, 2022)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (August 31, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 31, 2022)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 31, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 31, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 31, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 31, 2022)
K-0900Meet Health Care Facilities Code mechanical requirements.Deficient, Provider has date of correction (August 31, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 31, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 31, 2022)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (August 31, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 31, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.