Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
AUTUMN LAKE HEALTHCARE AT CALVERT MANOR
RISING SUN, MD · 144 certified beds · Last Life Safety survey May 28, 2026
CMS Certification Number 215189 · first certified June 1989
Ownership
Operated by AUTUMN LAKE HEALTHCARE · For profit - Limited Liability company
- Ownership changed August 1, 2022 (change of ownership)from AXIS HEALTH AT CALVERT OPCO LLC
Position within MD
36 citations — more than 90% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 1 citation; the earlier surveys in the window averaged 11.7. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2027 — about 13 months from now. This facility’s last Life Safety survey was May 2026. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about AUTUMN LAKE HEALTHCARE AT CALVERT MANOR
One email when it happens. No account; stop it any time with one click.
2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Physical environment (health survey)
2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 36 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 36 |
| Median facility in MD | 22 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| December 17, 2018 | 1 |
| October 18, 2022 | 19 |
| April 2, 2025 | 15 |
| May 28, 2026 | 1 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0271 | Have exits that are accessible at all times. | 2 | 2025-04-02 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-04-02 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2025-04-02 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2025-04-02 |
| K-0541 | Install properly constructed and protected linen or trash chutes. | 2 | 2025-04-02 |
| K-0224 | Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion. | 1 | 2025-04-02 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 1 | 2022-10-18 |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | 1 | 2025-04-02 |
What the citations cover
- Smoke Deficiencies 14
- Services Deficiencies 7
- Egress Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 4
- Other 4
| Category | Citations |
|---|---|
| Smoke Deficiencies | 14 |
| Services Deficiencies | 7 |
| Egress Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 4 |
| Miscellaneous Deficiencies | 3 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 28, 2026 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (July 30, 2026) |
April 2, 2025 — 15 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0224 | Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (May 29, 2025) |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | Deficient, Provider has date of correction (May 29, 2025) |
October 18, 2022 — 19 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0525 | Enure that solid fuel-burning fireplaces are not in patient sleeping areas. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 30, 2022) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (December 30, 2022) |
December 17, 2018 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (February 18, 2019) |