Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
BAY HARBOR POST ACUTE HEALTHCARE CENTER
SALISBURY, MD · 305 certified beds · Last Life Safety survey April 17, 2026
CMS Certification Number 215067 · first certified July 1969
Ownership
Operated by MARQUIS HEALTH SERVICES · For profit - Limited Liability company
- Ownership changed July 1, 2024 (change of ownership)to BAY HARBOR POST ACUTE AND HEALTHCARE CENTER from PENINSULA REGIONAL-GENESIS ELDERCARE LLC
Position within MD
44 citations — more than 96% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 15 citations; the earlier surveys on file averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens August 2027 — about 9 months from now. This facility’s last Life Safety survey was April 2026. Facilities in MD are typically surveyed 16–48 months after the last one (median 23), measured over 307 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured
Get an email about BAY HARBOR POST ACUTE HEALTHCARE CENTER
One email when it happens. No account; stop it any time with one click.
7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Physical environment (health survey)
17 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
- F-0908 Keep all essential equipment working safely.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 44 |
| Median facility in MD | 23 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| October 16, 2019 | 8 |
| January 17, 2025 | 21 |
| April 17, 2026 | 15 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-04-17 |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | 2 | 2026-04-17 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 2 | 2026-04-17 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2026-04-17 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2025-01-17 |
| K-0351 | Install an approved automatic sprinkler system. | 2 | 2025-01-17 |
| K-0100 | Meet other general requirements. | 2 | 2026-04-17 |
| K-0500 | Meet other general requirements that are deficient. | 2 | 2025-01-17 |
What the citations cover
- Smoke Deficiencies 16
- Egress Deficiencies 8
- Miscellaneous Deficiencies 6
- Services Deficiencies 6
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 16 |
| Egress Deficiencies | 8 |
| Miscellaneous Deficiencies | 6 |
| Services Deficiencies | 6 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 5 |
| Construction Deficiencies | 3 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 17, 2026 — 15 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 29, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (July 29, 2026) |
January 17, 2025 — 21 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Waiver has been granted (April 22, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Waiver has been granted (April 22, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0500 | Meet other general requirements that are deficient. | Waiver has been granted (April 22, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Waiver has been granted (April 22, 2025) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (April 22, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (April 22, 2025) |
October 16, 2019 — 8 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (January 20, 2020) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (January 20, 2020) |