Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BAY HARBOR POST ACUTE HEALTHCARE CENTER

SALISBURY, MD · 305 certified beds · Last Life Safety survey January 17, 2025

CMS Certification Number 215067 · first certified July 1969

Ownership

Operated by MARQUIS HEALTH SERVICES · For profit - Limited Liability company

  • Ownership changed July 1, 2024 (change of ownership)to BAY HARBOR POST ACUTE AND HEALTHCARE CENTER from PENINSULA REGIONAL-GENESIS ELDERCARE LLC
35
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within MD

35 citations — more than 86% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 21 citations; the earlier surveys in the window averaged 7. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: June 2026 to December 2029. This facility’s last Life Safety survey was January 2025. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BAY HARBOR POST ACUTE HEALTHCARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

15 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 35 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0908 Keep all essential equipment working safely.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility35MD median22National median11
Citations on file over three years, compared
MeasureCitations
This facility35
Median facility in MD22
Median facility nationally11

Survey history

Citations at each Life Safety survey
62018-0682019-10212025-01
Citations at each Life Safety survey
Survey dateCitations
June 18, 20186
October 16, 20198
January 17, 202521

Most-cited tags

Most-cited tags at this facility
K-03513K-02232K-03452K-05412K-03532K-05002K-07612K-03212
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0351Install an approved automatic sprinkler system.32025-01-17
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.22019-10-16
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-01-17
K-0541Install properly constructed and protected linen or trash chutes.22025-01-17
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-01-17
K-0500Meet other general requirements that are deficient.22025-01-17
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22025-01-17
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22025-01-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Egress Deficiencies 6
  • Services Deficiencies 6
  • Miscellaneous Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Egress Deficiencies6
Services Deficiencies6
Miscellaneous Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies3
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 17, 2025 — 21 citations

Citations issued on January 17, 2025
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (April 22, 2025)
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (April 22, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 22, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 22, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 22, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted (April 22, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 22, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (April 22, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (April 22, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 22, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (April 22, 2025)
K-0500Meet other general requirements that are deficient.Waiver has been granted (April 22, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 22, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (April 22, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (April 22, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 22, 2025)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (April 22, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 22, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 22, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (April 22, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 22, 2025)

October 16, 2019 — 8 citations

Citations issued on October 16, 2019
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (January 20, 2020)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (January 20, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 20, 2020)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (January 20, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 20, 2020)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 20, 2020)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (January 20, 2020)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (January 20, 2020)

June 18, 2018 — 6 citations

Citations issued on June 18, 2018
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 22, 2018)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (June 22, 2018)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 22, 2018)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (July 25, 2018)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 22, 2018)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (June 22, 2018)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.