Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Wicomico Nursing Home

SALISBURY, MD · 102 certified beds · Last Life Safety survey February 5, 2026

CMS Certification Number 215007 · first certified September 1972

Ownership

Independently operated (no chain recorded by CMS) · Government - County

No change of ownership on CMS record since January 1, 2016, when the records begin.

One or more citations below are marked by CMS as under Informal Dispute Resolution.
34
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within MD

34 citations — more than 83% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was February 2026. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Wicomico Nursing Home

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 34 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility34MD median22National median11
Citations on file over three years, compared
MeasureCitations
This facility34
Median facility in MD22
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-06162024-0892026-02
Citations at each Life Safety survey
Survey dateCitations
June 13, 20199
August 29, 202416
February 5, 20269

Most-cited tags

Most-cited tags at this facility
K-09183K-03533K-07542K-09192K-07612K-07122K-03212K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-02-05
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-02-05
K-0754Provide properly sized and located linen or trash receptacles.22024-08-29
K-0919Meet requirements for the use of electrical equipment.22024-08-29
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22024-08-29
K-0712Have simulated fire drills held at unexpected times.22026-02-05
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-08-29
K-0324Provide properly protected cooking facilities.22024-08-29

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Miscellaneous Deficiencies 7
  • Egress Deficiencies 5
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies8
Miscellaneous Deficiencies7
Egress Deficiencies5
Construction Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 5, 2026 — 9 citations

Citations issued on February 5, 2026
TagWhat the surveyor checksStatus
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (March 27, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 27, 2026) · under dispute
K-0224Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion.Deficient, Provider has date of correction (March 27, 2026) · under dispute
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (March 27, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 27, 2026) · under dispute
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 27, 2026)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (March 27, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 27, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 27, 2026)

August 29, 2024 — 16 citations

Citations issued on August 29, 2024
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (October 22, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 22, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 22, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 22, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 22, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (October 22, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 22, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 22, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (October 22, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 22, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (October 22, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 22, 2024)
K-0771Ensure that smoke control systems are tested and documented in accordance with established engineering principles.Deficient, Provider has date of correction (October 22, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 22, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 22, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (October 22, 2024)

June 13, 2019 — 9 citations

Citations issued on June 13, 2019
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 1, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 1, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 1, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 1, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 1, 2019)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (October 1, 2019)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 1, 2019)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 1, 2019)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (October 1, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.