Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

SOLOMONS NURSING AND REHAB CENTER

SOLOMONS, MD · 95 certified beds · Last Life Safety survey February 2, 2026

CMS Certification Number 215270 · first certified November 1994

Ownership

Operated by GREEN TREE HEALTHCARE MANAGEMENT · For profit - Individual

  • Ownership changed September 1, 2020 (change of ownership)from SOLOMONS NURSING CENTER INC
38
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within MD

38 citations — more than 93% of the 221 certified nursing homes in MD. Compared within MD rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was February 2026. Facilities in MD are typically surveyed 17–59 months after the last one (median 30), measured over 283 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about SOLOMONS NURSING AND REHAB CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0923 Have enough outside ventilation via a window or mechanical ventilation, or both.
  • F-0908 Keep all essential equipment working safely.

How that compares

Citations on file over three years

Compared with the median facility in MD, and nationally. Surveyors differ markedly between states, so the MD figure is the meaningful one.

This facility38MD median22National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in MD22
Median facility nationally11

Survey history

Citations at each Life Safety survey
62019-09202024-08122026-02
Citations at each Life Safety survey
Survey dateCitations
September 13, 20196
August 29, 202420
February 2, 202612

Most-cited tags

Most-cited tags at this facility
K-03533K-07613K-03243K-03633K-03452K-09202K-09142K-09232
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-02-02
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32026-02-02
K-0324Provide properly protected cooking facilities.32026-02-02
K-0363Install corridor and hallway doors that block smoke.32026-02-02
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-02-02
K-0920Ensure proper usage of power strips and extension cords.22026-02-02
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22026-02-02
K-0923Have proper medical gas storage and administration areas.22026-02-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 4
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies9
Egress Deficiencies7
Miscellaneous Deficiencies4
Emergency Preparedness Deficiencies2
Construction Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 2, 2026 — 12 citations

Citations issued on February 2, 2026
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (March 20, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 15, 2026)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 20, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 20, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 15, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 15, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 15, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 15, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 20, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 15, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 20, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 15, 2026)

August 29, 2024 — 20 citations

Citations issued on August 29, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (November 12, 2024)
K-0100Meet other general requirements.Deficient, Provider has date of correction (October 10, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 12, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 10, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (October 10, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 10, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 10, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 10, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (October 10, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 12, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 12, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 10, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (October 10, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 10, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (October 10, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 10, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 10, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 12, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 10, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (October 10, 2024)

September 13, 2019 — 6 citations

Citations issued on September 13, 2019
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 1, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 1, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 1, 2019)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 1, 2019)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 1, 2019)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 1, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.