Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
CLOVER HEALTH CARE
AUBURN, ME · 109 certified beds · Last Life Safety survey May 9, 2025
CMS Certification Number 205063 · first certified July 1990
Ownership
Operated by SENIOR LIFESTYLE · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within ME
52 citations — more than 100% of the 78 certified nursing homes in ME. Compared within ME rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 30 citations; the earlier surveys in the window averaged 11. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Past the typical window (June 2026 to August 2026). Most ME facilities have been surveyed by October 2027. This facility’s last Life Safety survey was May 2025. Facilities in ME are typically surveyed 13–15 months after the last one (median 14), measured over 115 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about CLOVER HEALTH CARE
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
14 of the 52 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
10 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 52 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
How that compares
Compared with the median facility in ME, and nationally. Surveyors differ markedly between states, so the ME figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 52 |
| Median facility in ME | 17 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| February 9, 2022 | 18 |
| February 9, 2024 | 4 |
| May 9, 2025 | 30 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3 | 2025-05-09 |
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-05-09 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2024-02-09 |
| K-0923 | Have proper medical gas storage and administration areas. | 2 | 2025-05-09 |
| E-0026 | Establish roles under a Waiver declared by secretary. | 2 | 2025-05-09 |
| E-0015 | Address subsistence needs for staff and patients. | 2 | 2025-05-09 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 2 | 2025-05-09 |
| K-0754 | Provide properly sized and located linen or trash receptacles. | 2 | 2024-02-09 |
What the citations cover
- Emergency Preparedness Deficiencies 14
- Smoke Deficiencies 12
- Miscellaneous Deficiencies 10
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Other 7
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 14 |
| Smoke Deficiencies | 12 |
| Miscellaneous Deficiencies | 10 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Egress Deficiencies | 5 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 9, 2025 — 30 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (June 16, 2025) |
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (June 16, 2025) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0163 | Install noncombustible or limited-combustible interior walls. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0753 | Have restrictions on the use of highly flammable decorations. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 16, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 16, 2025) |
February 9, 2024 — 4 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 26, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 26, 2024) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (March 26, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (March 26, 2024) |
February 9, 2022 — 18 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (March 29, 2022) |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (March 29, 2022) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (March 29, 2022) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (March 29, 2022) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0331 | Construct fire resistant interior walls. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 29, 2022) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (March 29, 2022) |