Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Mission Point Nursing & Physical Rehabilitation Ce

Detroit, MI · 129 certified beds · Last Life Safety survey May 15, 2026

CMS Certification Number 235468 · first certified May 1988

Ownership

Operated by MISSION POINT HEALTHCARE SERVICES · For profit - Corporation

  • Ownership changed December 17, 2020 (change of ownership)to MISSION POINT NURSING & PHYSICAL REHABILITATION CENTER OF WOODWARD from THE BAY AT WOODWARD HEALTH AND REHABILITATION CENTER, LLC
44
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within MI

44 citations — more than 99% of the 422 certified nursing homes in MI. Compared within MI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 11 citations; the earlier surveys in the window averaged 16.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens May 2027 — about 7 months from now. This facility’s last Life Safety survey was May 2026. Facilities in MI are typically surveyed 12–14 months after the last one (median 13), measured over 723 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Mission Point Nursing & Physical Rehabilitation Ce

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 44 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0908 Keep all essential equipment working safely.

How that compares

Citations on file over three years

Compared with the median facility in MI, and nationally. Surveyors differ markedly between states, so the MI figure is the meaningful one.

This facility44MI median14National median11
Citations on file over three years, compared
MeasureCitations
This facility44
Median facility in MI14
Median facility nationally11

Survey history

Citations at each Life Safety survey
202024-02132025-03112026-05
Citations at each Life Safety survey
Survey dateCitations
February 1, 202420
March 5, 202513
May 15, 202611

Most-cited tags

Most-cited tags at this facility
K-07123K-03533K-05113K-02233K-03243K-09232K-03632K-09182
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32026-05-15
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-05-15
K-0511Have properly installed electrical wiring and gas equipment.32026-05-15
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.32026-05-15
K-0324Provide properly protected cooking facilities.32026-05-15
K-0923Have proper medical gas storage and administration areas.22025-03-05
K-0363Install corridor and hallway doors that block smoke.22026-05-15
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-03-05

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 7
  • Services Deficiencies 6
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Egress Deficiencies7
Miscellaneous Deficiencies7
Services Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies5
Emergency Preparedness Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 15, 2026 — 11 citations

Citations issued on May 15, 2026
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (July 7, 2026)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (July 7, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 7, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 7, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 7, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 7, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 7, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (July 7, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 7, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 7, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 7, 2026)

March 5, 2025 — 13 citations

Citations issued on March 5, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 15, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (April 15, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 15, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 15, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 15, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 15, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 15, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 15, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 15, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 15, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 15, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 15, 2025)
K-0925Ensure that sources of ignition are removed from patients receiving respiratory therapy.Deficient, Provider has date of correction (April 15, 2025)

February 1, 2024 — 20 citations

Citations issued on February 1, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (April 1, 2024)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (April 1, 2024)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (April 1, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 25, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (April 1, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 5, 2024)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (March 25, 2024)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (April 1, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (March 25, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 1, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 25, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 25, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (April 5, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 1, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (April 1, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 25, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 1, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (April 1, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 1, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 1, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.