Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

The Orchards at Wayne

Wayne, MI · 179 certified beds · Last Life Safety survey November 21, 2025

CMS Certification Number 235521 · first certified May 1992

Ownership

Operated by THE ORCHARDS MICHIGAN · For profit - Corporation

  • Ownership changed November 1, 2021 (change of ownership)from RHEMA WTLC OPERATING LLC
38
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within MI

38 citations — more than 97% of the 422 certified nursing homes in MI. Compared within MI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 16. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 2 months from now. This facility’s last Life Safety survey was November 2025. Facilities in MI are typically surveyed 12–14 months after the last one (median 13), measured over 723 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about The Orchards at Wayne

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.

How that compares

Citations on file over three years

Compared with the median facility in MI, and nationally. Surveyors differ markedly between states, so the MI figure is the meaningful one.

This facility38MI median14National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in MI14
Median facility nationally11

Survey history

Citations at each Life Safety survey
182023-05142024-0862025-11
Citations at each Life Safety survey
Survey dateCitations
May 22, 202318
August 1, 202414
November 21, 20256

Most-cited tags

Most-cited tags at this facility
K-09183K-03533K-05113K-03242K-05212K-02232K-03552E-00392
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-11-21
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-21
K-0511Have properly installed electrical wiring and gas equipment.32025-11-21
K-0324Provide properly protected cooking facilities.22024-08-01
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22025-11-21
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.22025-11-21
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22024-08-01
E-0039Conduct testing and exercise requirements.22024-08-01

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Egress Deficiencies 6
  • Services Deficiencies 5
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies6
Egress Deficiencies6
Services Deficiencies5
Miscellaneous Deficiencies4
Emergency Preparedness Deficiencies4
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 21, 2025 — 6 citations

Citations issued on November 21, 2025
TagWhat the surveyor checksStatus
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (December 3, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (December 3, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 3, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 3, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 3, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 3, 2025)

August 1, 2024 — 14 citations

Citations issued on August 1, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (September 12, 2024)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (September 12, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 12, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (September 12, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 12, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (September 12, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 12, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 12, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 12, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 12, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 12, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 12, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 12, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 12, 2024)

May 22, 2023 — 18 citations

Citations issued on May 22, 2023
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 30, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 30, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 30, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 30, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 30, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 30, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 30, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 30, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 30, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 30, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 30, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (June 30, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (June 30, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 30, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 30, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 30, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 30, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 30, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.