Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Westland, A Villa Center

Westland, MI · 230 certified beds · Last Life Safety survey March 20, 2025

CMS Certification Number 235332 · first certified June 1977

Ownership

Operated by VILLA HEALTHCARE · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

23
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within MI

23 citations — more than 79% of the 422 certified nursing homes in MI. Compared within MI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 7. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten MI facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in MI are typically surveyed 12–14 months after the last one (median 13), measured over 723 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Westland, A Villa Center

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 23 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 23 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in MI, and nationally. Surveyors differ markedly between states, so the MI figure is the meaningful one.

This facility23MI median14National median11
Citations on file over three years, compared
MeasureCitations
This facility23
Median facility in MI14
Median facility nationally11

Survey history

Citations at each Life Safety survey
62022-1182024-0292025-03
Citations at each Life Safety survey
Survey dateCitations
November 3, 20226
February 8, 20248
March 20, 20259

Most-cited tags

Most-cited tags at this facility
K-05113K-03532K-03512K-03552K-09182K-03211K-03631K-09231
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0511Have properly installed electrical wiring and gas equipment.32025-03-20
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-03-20
K-0351Install an approved automatic sprinkler system.22025-03-20
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-03-20
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-03-20
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12024-02-08
K-0363Install corridor and hallway doors that block smoke.12024-02-08
K-0923Have proper medical gas storage and administration areas.12024-02-08

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 10
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Services Deficiencies 3
  • Miscellaneous Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies10
Gas, Vacuum, and Electrical Systems Deficiencies5
Services Deficiencies3
Miscellaneous Deficiencies2
Egress Deficiencies2
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 20, 2025 — 9 citations

Citations issued on March 20, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Waiver has been granted
K-0351Install an approved automatic sprinkler system.Waiver has been granted (June 6, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 29, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 29, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (April 29, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 29, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 29, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 29, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 29, 2025)

February 8, 2024 — 8 citations

Citations issued on February 8, 2024
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 11, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 11, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 11, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 11, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 11, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (March 11, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 11, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 11, 2024)

November 3, 2022 — 6 citations

Citations issued on November 3, 2022
TagWhat the surveyor checksStatus
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (December 16, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 16, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 16, 2022)
K-0371Have properly sized and located compartments to protect residents from smoke.Deficient, Provider has date of correction (December 16, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 16, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 16, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.