Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

EDENBROOK PINE HAVEN

PINE ISLAND, MN · 70 certified beds · Last Life Safety survey July 17, 2026

CMS Certification Number 245359 · first certified November 1986

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

  • New ownershipOwnership changed September 1, 2025 (change of ownership)from PINE HAVEN INC
30
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
8
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within MN

30 citations — more than 96% of the 337 certified nursing homes in MN. Compared within MN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 13 citations; the earlier surveys on file averaged 8.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 7 months from now. This facility’s last Life Safety survey was July 2026. Facilities in MN are typically surveyed 11–14 months after the last one (median 13), measured over 641 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about EDENBROOK PINE HAVEN

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in MN, and nationally. Surveyors differ markedly between states, so the MN figure is the meaningful one.

This facility30MN median12National median11
Citations in CMS's current file, compared
MeasureCitations
This facility30
Median facility in MN12
Median facility nationally11

Survey history

Citations at each Life Safety survey
132024-0742025-08132026-07
Citations at each Life Safety survey
Survey dateCitations
July 17, 202413
August 28, 20254
July 17, 202613

Most-cited tags

Most-cited tags at this facility
K-07123K-03533K-03722K-09182K-09262K-09202K-09142K-03452
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32026-07-17
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-07-17
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-07-17
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-08-28
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.22026-07-17
K-0920Ensure proper usage of power strips and extension cords.22026-07-17
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22026-07-17
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22026-07-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Miscellaneous Deficiencies 6
  • Electrical Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies9
Miscellaneous Deficiencies6
Electrical Deficiencies1
Egress Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 17, 2026 — 13 citations

Citations issued on July 17, 2026
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (September 21, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has plan of correction
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 21, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 24, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 21, 2026)
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has date of correction (August 31, 2026)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (September 21, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 31, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 21, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 31, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 24, 2026)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (September 21, 2026)

August 28, 2025 — 4 citations

Citations issued on August 28, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 15, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 15, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 15, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 15, 2025)

July 17, 2024 — 13 citations

Citations issued on July 17, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 26, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 26, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 26, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 26, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 26, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (August 26, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 26, 2024)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (August 26, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 26, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 26, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 26, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 26, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (August 26, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.