Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WOODBURY HEALTH CARE CENTER

WOODBURY, MN · 155 certified beds · Last Life Safety survey July 16, 2026

CMS Certification Number 245235 · first certified June 1981

Ownership

Operated by LIFESPARK · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

30
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
9
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within MN

30 citations — more than 96% of the 337 certified nursing homes in MN. Compared within MN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 4 citations; the earlier surveys on file averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 7 months from now. This facility’s last Life Safety survey was July 2026. Facilities in MN are typically surveyed 11–14 months after the last one (median 13), measured over 641 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about WOODBURY HEALTH CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations in CMS's current file

Compared with the median facility in MN, and nationally. Surveyors differ markedly between states, so the MN figure is the meaningful one.

This facility30MN median12National median11
Citations in CMS's current file, compared
MeasureCitations
This facility30
Median facility in MN12
Median facility nationally11

Survey history

Citations at each Life Safety survey
122024-06142025-0742026-07
Citations at each Life Safety survey
Survey dateCitations
June 27, 202412
July 24, 202514
July 16, 20264

Most-cited tags

Most-cited tags at this facility
K-09202K-07122K-03242K-03552K-05412K-03532K-09232K-09182
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.22025-07-24
K-0712Have simulated fire drills held at unexpected times.22025-07-24
K-0324Provide properly protected cooking facilities.22026-07-16
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-07-24
K-0541Install properly constructed and protected linen or trash chutes.22025-07-24
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-07-24
K-0923Have proper medical gas storage and administration areas.22026-07-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-07-16

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 13
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Miscellaneous Deficiencies 3
  • Services Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies13
Gas, Vacuum, and Electrical Systems Deficiencies10
Miscellaneous Deficiencies3
Services Deficiencies2
Egress Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 16, 2026 — 4 citations

Citations issued on July 16, 2026
TagWhat the surveyor checksStatus
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 6, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 6, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 6, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 6, 2026)

July 24, 2025 — 14 citations

Citations issued on July 24, 2025
TagWhat the surveyor checksStatus
K-0162Have a combustible roofing system that meets safety standards.Deficient, Provider has date of correction (October 1, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 1, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 1, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 1, 2025)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 1, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 1, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 1, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 1, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 1, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (October 1, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 1, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 1, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 1, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 1, 2025)

June 27, 2024 — 12 citations

Citations issued on June 27, 2024
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 8, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 8, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 16, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 30, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (July 2, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 28, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 27, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 27, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 10, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (August 30, 2024)
K-0930Ensure proper storage of liquid oxygen.Deficient, Provider has date of correction (June 26, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.