Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PARKSIDE MANOR

COLUMBIA, MO · 120 certified beds · Last Life Safety survey December 19, 2024

CMS Certification Number 265302 · first certified March 1986

Ownership

Operated by JAMES & JUDY LINCOLN · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

38
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within MO

38 citations — more than 91% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 15 citations; the earlier surveys in the window averaged 7.7. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (February 2026 to September 2026). Most MO facilities have been surveyed by November 2026. This facility’s last Life Safety survey was December 2024. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PARKSIDE MANOR

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility38MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
162022-0762023-0812024-09152024-12
Citations at each Life Safety survey
Survey dateCitations
July 28, 202216
August 23, 20236
September 19, 20241
December 19, 202415

Most-cited tags

Most-cited tags at this facility
K-03453K-03722K-07412K-07122K-09142K-05112K-03632K-09232
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32024-12-19
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-12-19
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-09-19
K-0712Have simulated fire drills held at unexpected times.22024-12-19
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22023-08-23
K-0511Have properly installed electrical wiring and gas equipment.22024-12-19
K-0363Install corridor and hallway doors that block smoke.22024-12-19
K-0923Have proper medical gas storage and administration areas.22024-12-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 13
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Services Deficiencies 5
  • Miscellaneous Deficiencies 5
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies13
Gas, Vacuum, and Electrical Systems Deficiencies10
Services Deficiencies5
Miscellaneous Deficiencies5
Egress Deficiencies3
Emergency Preparedness Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

December 19, 2024 — 15 citations

Citations issued on December 19, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (January 30, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (January 30, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 30, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 30, 2025)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (January 30, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 30, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 30, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 30, 2025)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (January 30, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 30, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (January 30, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 30, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 30, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 30, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 30, 2025)

September 19, 2024 — 1 citation

Citations issued on September 19, 2024
TagWhat the surveyor checksStatus
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 31, 2024)

August 23, 2023 — 6 citations

Citations issued on August 23, 2023
TagWhat the surveyor checksStatus
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (October 4, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 4, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (October 4, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 4, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (October 4, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 4, 2023)

July 28, 2022 — 16 citations

Citations issued on July 28, 2022
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 8, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 8, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 8, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 8, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 8, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 8, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 8, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 8, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 8, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 8, 2022)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (September 8, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 8, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 8, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 8, 2022)
K-0925Ensure that sources of ignition are removed from patients receiving respiratory therapy.Deficient, Provider has date of correction (September 8, 2022)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (September 8, 2022)